Rosemount ™ 6888 Product Certifications - Emerson Rosemount 6888C Quick Start Manual

In-situ combustion oxygen analyzer for use in hazardous areas
Hide thumbs Also See for Rosemount 6888C:

Advertisement

October 2019
A
Rosemount
Rev 1.9
A.1
European Directive information
The most recent revision of the EU Declaration of Conformity can be found
at Emerson.com/Rosemount.
A.2
Ordinary location certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
A.3
Installing equipment in North America
The US National Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The marking must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
A.4
USA/Canada
Model String
Option Code
CSA
Certificate
Standards
Markings
Quick Start Guide
6888 product certifications
®
(NEC) and the Canadian Electrical Code
C
70100758
CAN/CSA Standard C22.2 No.0-10:2015, CAN/CSA C22.2
No.61010-1-12 Harmonized UL 61010-1:2012 (3rd
Edition), CAN/CSA Standard C22.2 No. 94.1-15
Harmonized ANSI/UL Standard 50 (2nd Edition), CAN/CSA
Standard C22.2 No. 94.2-15 Harmonized ANSI/UL Standard
50 (2nd Edition), CAN/CSA C22.2 No. 60529:16 and
ANSI/ISA 60529:04, CAN/CSA Standard C22.2 No. 30-
M1986: 2016, CAN/CSA-C22.2 No. 60079-0: 2015, CAN/
CSA-C22.2 No. 60079-1:2016, FM 3600:2011, FM
3615:2006, ANSI/UL-60079-0:2013 (6th Edition), ANSI/
UL-60079-1:2015 (7th Edition)
Type 4X, IP66, Class 1, Division 1, Groups B, C and D;
T3, Class 1, Zone 1, AEx db IIB+H2 T3 Gb, Ex db IIB+H2 T3
Gb: -40 °C ≤ Ta ≤ +70 °C ( Autocal Housing and Probe
assembly); -40 °C ≤ Ta ≤ +90 °C (Standard Housing and
Probe assembly eq. "DR Probe")
Quick Start Guide
31