Quick Start Guide
The Rosemount 6888C accepts line voltage at 120/240 Vac ±10%,
50/60 Hz. No setup is required.
3. Connect the 4-20 mA signal wires at the transmitter. Use a shielded
twisted wire pair. Do not allow bare shield wires to contact the circuit
boards. Insulate the shield wires prior to termination.
The transmitter electronics are loop-powered (i.e., the 4-20 mA
signal wires supply 24 Vdc from the DCS or an external power
supply).
Figure 1-5: Rosemount 6888C Standard Probe Housing
4. Terminate the shield only at the transmitter electronics housing
unless using a Rosemount 6888 Xi. When using the Rosemount 6888
Xi Advanced Electronics, terminate the shield at both ends.
5. Reinstall cover on transmitter.
1.2.2
Wire standard housing transmitter probe with Rosemount
Electronics
The Rosemount 6888 Xi Electronics serves as an operater interface unit with
a back-lit display and keypad. It is capable of two channels, serving up to two
Rosemount 6888 probes.
Procedure
1. Remove cover screws from the front cover of the Rosemount 6888
Xi. Swing down the front cover of the interface box.
10
October 2019
6888 Xi