The out-of-box settings of an Energi Savr Node QS unit can be changed to customize the installation. Please
follow the steps described below to adjust the settings on your Energi Savr Node QS unit.

Input Programming Mode

* N ote: After 10 minutes without activity on the user interface, the Energi Savr Node QS unit will automatically
exit the Input Programming Mode. The Energi Savr Node QS unit will retain the latest changes.
Assign/Unassign zones to wired sensors
1. To enter Input Programming Mode, press and hold the Program button for 3 seconds. The 'Program' LED will
blink.
2. Press Program button to sequence through each sensor input. The LED corresponding to the selected
sensor input will blink. If powered by the Energi Savr Node QS unit, the sensor will flash also.*
3. For each desired zone, press & hold the Zone button until the LED changes state to assign or un-assign that
zone. A blinking 'Zone' LED indicates that a zone is assigned.
4. To exit Input Programming Mode, press and hold the Program button for 3 seconds.
Note: Before assigning a daylight sensor to a zone, you must first unassociate any previously assigned sensors
from that zone, including those in out-of-box mode.
* Only sensors powered directly from the Energi Savr Node QS unit will flash.

Sensor Overview

Occupancy Sensors
Energi Savr Node QS units are programmable to turn lights on and off based on room occupancy detected by
compatible occupancy sensors. To ensure proper operation of the Energi Savr Node QS unit:
• Wire no more than 2 occupancy sensors to any one Occ connection. An auxiliary power supply must be used
if the device(s) require(s) more than 50 mA.
Daylight Sensors
Energi Savr Node QS units are programmable to turn lights on and off based on daylight detected by
compatible Lutron
daylight sensors. To ensure proper operation of the Energi Savr Node QS unit:
®
• Use only Lutron daylight sensors (EC-DIR-WH).
• Only wire one sensor to a single Photo input.
Each zone output on an Energi Savr Node QS unit can be programmed to respond to a single daylight sensor.
The target setpoint for turn-on/turn-off is adjustable for each zone—one sensor may be linked to multiple
zones, each zone with its own unique setpoint. Please note that:
• A daylight sensor wired to an Energi Savr Node QS unit can be assigned to control any or all zones on that
Energi Savr Node QS unit.
• Daylight sensors will not turn a zone on if an occupancy sensor assigned to that zone detects that the room is
vacant.
|