Energi Savr Node
5. Exit Scene Programming Mode: Press and hold the Program and Option buttons for 3 seconds.
Scenes 5-16
1. Simultaneously press and hold the Program and Option buttons on the Energi Savr Node QS unit for 3
seconds to enter Scene Programming Mode. 'Program' and Group B LEDs will flash rapidly.
2. Press and hold the Option button on the Energi Savr Node QS unit for 10 seconds to access Scenes 5-16.
Scene selections are indicated by flashing Option LEDs as shown ion the chart below:
LED Legend:
= steady on
LEDs
Scene # LEDs
Scene 5
Scene 9
Scene 13
3. Use the and buttons to set the selected scene to On or Off. The 'H', 'M', and 'L' LED group indicates your
choice: all LEDs on = On; all LEDs off = Off.
4. To make a zone unaffected, press and hold the button until the 'Zone' LED turns off and the 'M' LED turns
on.
5. If necessary, you may press and hold the Option button on the Energi Savr Node QS unit for 10 seconds to
return to Scenes 1-4.
6. Exit Scene Set-up Mode: Press and hold the Program and Option buttons for 3 seconds.
|
Energi Savr Node
QS
TM
QS | Programming Guide
TM
= flashing
Scene # LEDs
Scene 6
Scene 10
Scene 14
Programming Guide
= off
Scene # LEDs
Scene #
Scene 7
Scene 8
Scene 11
Scene 12
Scene 15
Scene 16
|