Qs Link Input(S) Setup - Lutron Electronics Energi Savr Node QS QSNE-4S10-D Programming Manual

Table of Contents

Advertisement

Energi Savr Node

QS Link Input(s) Setup

To assign a seeTouch
QS link, follow the steps below.
seeTouch QS Wallstation - Scenes and Scenes + Off
1. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds. The QS link
enters Programming Mode. The sensor Group A and Group B LEDs and the 'H', 'M', and 'L' LEDs on the
Energi Savr Node QS unit(s) will flash sequentially in groups.
2. Use the Option button to select the scene wallstation type. A blinking LED indicates the selection:
• 'Def' LED indicates a 'scene + off' wallstation (wallstation has a specific Off button)
• 'Opt 1' LED indicates a 'scene' wallstation (wallstation has no Off button)
3. To save the wallstation type, press and hold the Option button for 3 seconds. The LED for the selected
wallstation type will flutter for 1 second, then remain steady.
4. To assign desired zone(s) to a wallstation, press and hold the Zone button for each desired zone for
3 seconds. A blinking 'Zone' LED indicates an assigned zone.
5. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds to save the
settings.
To un-assign Energi Savr Node QS unit zones from a specific wallstation, press and hold the Zone button for
the assigned zone(s) for 3 seconds. The 'Zone' LED will turn off to indicate success.
Repeat for each desired wallstation-to-zone set-up that you wish to un-assign.
seeTouch QS Wallstation - Zone Toggle Type
1. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds. The QS link
enters Programming Mode. The sensor Group A and Group B LEDs and the 'H', 'M', and 'L' LEDs on the
Energi Savr Node QS unit(s) will flash sequentially in groups.
2. Use the Option button to change the wallstation type to zone toggle. A blinking LED will indicate the selection.
Select 'Opt 2'.
3. To save the wallstation type, press and hold the Option button for 3 seconds. The LED for the selected
wallstation type will flutter for 1 second, then go to an on state.
4. To assign a specific wallstation button(s) to an Energi Savr Node QS unit zone, press the wallstation button you
wish to assign (e.g. press button 1 – LED blinks slowly).
5. Press and hold the Zone button for the desired zone for 3 seconds. A blinking 'Zone' LED indicates an
assigned zone.
6. Repeat steps 4-5 for each desired button-to-zone assignment.
7. Simultaneously press and hold the top and bottom buttons on the wallstation for 3 seconds to save the
settings.
To un-assign Energi Savr Node QS unit zones from specific wallstation buttons, press and hold the Zone
button for the assigned zone(s) for 3 seconds. The 'Zone' LED will turn off to indicate success.
GRAFIK Eye QS unit - Scenes and Scenes + Off
1. Simultaneously press and hold the top and bottom scene buttons on the GRAFIK Eye QS unit for 3 seconds.
The QS link enters Programming Mode. The sensor Group A and Group B LEDs and the 'H', 'M', and 'L' LEDs
on the Energi Savr Node QS unit(s) will flash sequentially in groups.
2. To assign desired zone(s) to a GRAFIK Eye QS unit, press and hold the Zone button for the desired zone for 3
seconds. A blinking 'Zone' LED indicates an assigned zone.
3. Simultaneously press and hold the top and bottom scene buttons on the GRAFIK Eye QS unit for 3 seconds to
save the settings.
|
Energi Savr Node
QS
TM
QS | Programming Guide
TM
QS Wallstation or GRAFIK Eye
®
Programming Guide
QS unit to any Energi Savr Node QS unit zone on the
®
|
Lutron
6
®

Hide quick links:

Advertisement

Table of Contents
loading