SNMP IPv6 for UPS
z
Transfer Voltage
After you click Submit to confirm your transfer voltage setup, the SNMP
IPv6 will send the command to the UPS to enable the relevant functions.
z
Low Battery
This configuration saves the setup values in the SNMP IPv6 and compares
with the values received from the UPS. If the received battery level is lower
than the assigned one, the SNMP IPv6 will trigger a low-battery alarm.
z
UPS Shutdown Action
This configuration saves your setup values in the SNMP IPv6 and compares
with the values received from the UPS. If an event like power failure or low
battery occurs, the SNMP IPv6 will send the assigned shutdown delay com-
mand to the UPS.
z
Smart Shutdown
The Smart Shutdown configuration is used to safely shutdown all of the
connected computers and the UPS. First of all, you should estimate the lon-
gest OS Shutdown Delay time for your operating systems that have been in-
stalled shutdown software and connected to the SNMP IPv6. The SNMP IPv6
will delay the assigned OS Shutdown Delay time and wait for all operating
systems' shutdown. After that, the SNMP IPv6 will send the assigned UPS
shutdown-delay command to the UPS and turn off the UPS.
z
Battery Replacement Date
After you set up battery replacement dates, the SNMP IPv6 will send the
command to the UPS and save the information in the UPS.
z
External Battery Pack
After you click Submit to confirm your external battery pack setup, the
SNMP IPv6 will send the command to the UPS and save the external battery
pack quantity in the UPS.
z
Bypass Transfer Frequency
After you set a tolerance of bypass transfer frequency and confirm your set-
up, the SNMP IPv6 will send the command to the UPS. If the UPS transfers to
bypass mode and the bypass frequency is out of the tolerance, output will
be turned off and critical loads will be protected.