February 2019
Note
It is recommended the cover be tightened until there is no gap between the
cover and the housing.
Figure 2-15: Simulate and Security Switches
A. Simulate disabled position
B. Simulate switch
C. Simulate enabled position
D. Security locked position
E. Security switch
F. Security unlocked position
2.5
Wire, ground, and power up
Use copper wire of sufficient size to ensure that the voltage across the
transmitter power terminals does not drop below 9 Vdc. Power supply voltage
can be variable, especially under abnormal conditions, such as when
operating on battery backup. Emerson
under normal operating conditions and shielded twisted pair Type A cable.
Procedure
1. To power the transmitter, connect the power leads to the terminals
indicated on the terminal block label.
Quick Start Guide
C
B
A
™
recommends a minimum of 12 Vdc
Quick Start Guide
D
E
F
15