Emerson 3051CF Series Quick Start Manual page 22

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for 3051CF Series:
Table of Contents

Advertisement

Quick Start Guide
Note
Step 1
through
guided setup, or on a single screen using manual setup.
Note
If the L_TYPE selected in
needed. If the L_TYPE selected is "Indirect",
unneeded steps will automatically be skipped.
Procedure
1. To select the signal conditioning "L_TYPE" from the drop down menu:
2. To set XD_SCALE to the 0% and 100% scale points (the transmitter
range):
3. If L_TYPE is "Indirect" or "Indirect Square Root", set OUT_SCALE to
change engineering units.
4. If L_TYPE is "Indirect Square Root", a LOW FLOW CUTOFF function is
available.
22
Step 4
are all performed in a single step by step method under
Step 1
a) Select L_TYPE: Direct for pressure measurements using the
device default units.
b) Select L_TYPE: Indirect for other pressure or level units.
c) Select L_TYPE: Indirect Square Root for flow units.
a) Select the XD_SCALE_UNITS from the drop down menu.
b) Enter the XD_SCALE 0% point. This may be elevated or
suppressed for level applications.
c) Enter the XD_SCALE 100% point. This may be elevated or
suppressed for level applications.
d) If L_TYPE is "Direct", the AI block may be placed in AUTO mode
to return the device to service. Guided setup does this
automatically.
a) Select the OUT_SCALE UNITS from the drop down menu.
b) Set the OUT_SCALE low value. This may be elevated or
suppressed for level applications.
c) Set the OUT_SCALE high value. This may be elevated or
suppressed for level applications.
d) If L_TYPE is "Indirect", the AI Block may be placed in AUTO
mode to return the device to service. Guided setup does this
automatically.
a) Enable LOW FLOW CUTOFF.
is "Direct",
Step
2,
Step 4
February 2019
Step 3
and
Step 4
are not
is not needed. Any
Emerson.com/Rosemount