5. Internal Memory
5.3. Operation parameter setting area
3.
The Rate Change alarm H./L. area is equivalent to the Rate Change alarm H./L.
configuration in I/O parameter setting window as shown in the following figure.

Rate change alarm detection period setting area (address 56~59)

1.
Area to set the detection interval, in case if you use Rate Change alarm function.
2.
If an out-of-range value is set, it sets 40ms internally; %UXa.b.24 ~ 27 (setting
error flag) is ON. The bit, 13 of setting error information area (address 60 ~ 63) is
ON.
88
Isolated Thermocouple Input Module TC4S User's Guide
Honeywell
R200
September 2010