5. Internal Memory
5.2. I/O area of TC module conversion data
Depending on the type of sensor and temperature metric system, it outputs temperature
conversion values within the following range.
K
-2600 ~ 13600
J
-2100 ~ 12100
E
-2600 ~ 10100
T
-2600 ~ 4100
B
3900 ~ 18100
R
- 600 ~ 17600
S
- 600 ~ 17600
N
-2800 ~ 13100
C
- 100 ~ 23100
ATTENTION

Channel scale operation value

1.
It outputs scale operation value for temperature conversion value to Address 8 ~11
(%UWa.b08~11) by channels.
RFERENCE - INTERNAL
For additional information, refer to Specifications.
2.
Scale operation value can be temporarily set as 16 bits data:−32768 ~ 32767 or 0 ~
65535.
70
Isolated Thermocouple Input Module TC4S User's Guide
Celsius(°)
Output range of temperature conversion value is within ±10°C margin of
the maximum temperature range.
For instance, in case of type K sensor, it indicates −10° of L and +10° of
H, -2600~13600.
The area is cleared if a channel stops (output 0 if it stops).
The temperature indication/settings in 2MLF-TC4S module displays
down to one decimal place (however, actually it does not display the
decimal point).
Honeywell
Fahrenheit[°F]
-4360 ~ 24800
-3460 ~ 22100
-4360 ~ 18500
-4360 ~ 7700
7340 ~ 32900
- 760 ~ 32000
- 760 ~ 32000
-4720 ~ 23900
140 ~ 41900