CAUTION
Mixing the modules can destroy them.
The terminal block is coded by inserting pins into designated
location holes on the terminal block in the base. This codes
the electronics modules to their respective terminal blocks.
1. Break off the coding pins on the coding comb such that the
comb is left with the coding combinations shown in Fig. 21.
2. The comb side corresponding to the respective terminal
block is inserted into the location holes in the terminal
block and broken off (positions 1 to 9 are printed on the
circuit board of the terminal block for alignment).
Fig. 22. Inserting coding comb into terminal block
3. Next, the other side of the comb is inserted into the elec-
tronics module location holes and likewise broken off. If
one or more opposing location holes both contain pins,
then the module cannot be mounted onto the terminal
block. The module can be mounted only if the single
coding pin corresponds to the missing pin in the terminal
block.
Fig. 23. Inserting coding comb into I/O module

Setting the Module Address

NOTE: The module address is set using the rotary HEX
switch (in the case of applications prior to CARE
4.0).
DISTRIBUTED I/O – PRODUCT DATA
All modules will report the setting of the 16-position rotary
HEX switch as a 2-byte ASCII number in the lowest 2 bytes of
the Neuron® chip's location string. Changing the rotary HEX
switch setting causes the module to reset its application
configuration (sensor selection, output selection, motor
runtime, etc.) and go unconfigured. Modules will run their
application in the unconfigured state so that another change
of the DIP switch will be recognized.
To remove the cover or a manual override module from the
Distributed I/O module, do the following:
1. Insert the cover release tool XAL2 into the corresponding
slots in the electronics module to release the locking tabs.
The tool should be inserted such that the marking is on the
right-hand side.
Fig. 24. Inserting opening tool
2. Lift off the cover as is depicted in Fig. 25.
Fig. 25. Lifting the cover off
IMPORTANT
Always use the XAL2 tool to remove the cover or a
manual override module from an output module. Lift off
manual override modules carefully to avoid tearing the
attached flat strip cable.