Operating and installation instructions REMKO ATK series Automatic oil heater with built-in oil burner and tank with exhaust gas connection ATK 25 Edition EN - Q08 Read the instructions prior to performing any task!
Content Safety notes Environmental protection and recycling Unit description Specifications for fan-assisted heaters Installation instructions Exhaust gas ducting Commissioning Shutdown Care and maintenance 10-12 Exhaust gas analysis Fuel pump Customer service and guarantee Intended use Electrical wiring diagram Troubleshooting Exploded view of the unit Spare parts list Maintenance log Technical data...
REMKO ATK series Environmental Safety notes protection Always observe the respective local building code and fire prevention and recycling guidelines as well as the guidelines of the accident prevention and insurance associations when using the units. Disposing of packaging The units have been subjected...
Unit description The units are portable, directly Operating sequence Safety temperature limiter fired fan-assisted heaters (WLE) (STB) with heat exchanger and exhaust The supply air fan switches on gas connections exclusively for once the units are switched The heating function is commercial applications.
REMKO ATK series Specifications for fan-assisted heaters is at least 10 times the nominal It is forbidden for personnel When using the units heating capacity in kW of all of to remain in these areas for the respective applicable guidelines must always the units operating in the space extended periods.
Installation instructions Installation in enclosed, well Safety distances The safety regulations of the accident prevention and ventilated areas without insurance associations, the exhaust gas connection In order to guarantee safe ■ respective regional building operation and maintenance regulations and the combustion The operation of the units is of the units, a 1.5 m safety ■...
REMKO ATK series Exhaust gas ducting It is also possible to operate the Fault-free operation is All parts of the exhaust gas ■ ■ units outdoors or in open spaces guaranteed if the exhaust gas ducting must be reliably without exhaust ducting.
Commissioning The units should be checked for Paraffin formation with low Connecting the units visible defects on the operating outside temperatures. to the electrical power supply and safety devices as well as proper installation and correct Even at low temperatures, an electrical connections before adequate supply of flowing 1.
REMKO ATK series Shutdown Care and maintenance Heating with room thermostat Regular care and observation (Accessories) 1. Move the operating of some basic requirements will switch to the "0" (Off) ensure trouble-free operation and The units operate fully position. a long service life of the units.
Page 11
Use only suitable cleaners, even Maintaining the burner ■ for heavy contamination Clean the burner components as described: Use only clean EL heating oil ■ or diesel fuel Beware of paraffin formation! The fuel tank must be emptied ■ and then rinsed with clean fuel at least twice a year Do not use water! Keep the burner head clean...
REMKO ATK series Exhaust gas analysis Setting the air slide The fuel tank must be cleaned: Due to the construction related design of the exhaust gas The air slide is factory set. After each heating period connection (connection nozzles with ■...
Fuel pump The pump works in the 1-pipe Adjustment of the pump pressure Cleaning the cartridge filter system as standard. The required fuel is sucked The pump pressure may only Clean the cartridge filter [B] of in by suction pipe S. be set and/or modified when the fuel pump at regular intervals a suitable oil pressure gauge is...
Failing to observe this renders and return the “Certificate of of their structural design and any manufacturer liability guarantee” to REMKO GmbH & equipment. or guarantee claims void. Co. KG at the time when the units are purchased and commissioned.
Troubleshooting Malfunctions Cause: The supply air fan does not start. 2 – 3 – 4 – 6 – 7 – 8 – 25 The supply air fan runs but the burner does not ignite. 1 – 5 – 6 – 9 – 10 – 11 – 12 – 13 – 14 – 15 – 16 – 17 The unit malfunctions without generating a flame.
REMKO ATK series Exploded view of the unit We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list Designation EDP no. Designation EDP no. Exhaust gas connection 1103702 Side section, right 1103771 Inspection cover 1103740 Side section, left 1103772 Cleaning cover 1103703 Locking ring 1101622 Seal 1103705 Hubcap 1101623 Combustion chamber compl. 1103728 Protective bracket, front 1102932 Air slide 1103729...
Technical data Series ATK 25 Nominal heat load max 25.00 Nominal heat capacity 22.50 Minimum heat capacity 22.50 Room heating emissions mg/kWh Air flow volume 1080 Temperature increase ΔT Fuel Heating oil EL acc. to DIN 51603 or diesel fuel fuel consumption 2.51 Max.