Operating and installation instructions
REMKO CLK series
Automatic oil/gas heaters
CLK 30, CLK 50, CLK 70, CLK 120, CLK 150
Edition GB - Q04
Read the instructions prior to performing any task!

Advertisement

Table of Contents
loading

Summary of Contents for REMKO CLK Series

  • Page 1 Operating and installation instructions REMKO CLK series Automatic oil/gas heaters CLK 30, CLK 50, CLK 70, CLK 120, CLK 150 Edition GB - Q04 Read the instructions prior to performing any task!
  • Page 3: Table Of Contents

    Content Safety notes Unit description Specifications for fan-assisted heaters Installation instructions Safety device Exhaust gas ducting Before commissioning Commissioning Shutdown Care and maintenance Troubleshooting Intended use Customer service and guarantee Environmental protection and recycling Electrical wiring diagram Exploded view of the unit Spare parts list Commissioning of forced-air oil burners Maintenance log...
  • Page 4: Safety Notes

    REMKO CLK SERIES Safety notes Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations when using the units. The units have been subjected Appropriate prohibition signs...
  • Page 5: Unit Description

    Heating or frost protection in on the automatic burner unit. ■ available as optional accessory) garden/agricultural outbuildings The temperature controller (TR) From CLK 120: REMKO ■ Operating sequence controls fan operation. Multiflex oil preheating If the units are set to heating...
  • Page 6: Specifications For Fan-Assisted Heaters

    REMKO CLK SERIES Specifications for fan- Installation instructions assisted heaters The units must not be used The safety regulations of the ■ below ground level, e.g. in When using the units the accident prevention and insurance respective applicable guidelines associations, the respective basements, without suitable gas must always be observed.
  • Page 7 Installation in enclosed, well Safety distances Electrical wiring ventilated areas without exhaust gas connection In order to guarantee safe The units are operated with ■ ■ operation and maintenance of 230 V/50 Hz alternating Reliable extraction of the the units, 1.5 m safety distance current ■...
  • Page 8: Safety Device

    REMKO CLK SERIES Safety equipment Safety temperature limiter Regulating devices The units have the following (STB) control or safety equipment: The temperature sensor of the The heating function is controller is self-monitoring. Temperature controller (TR) ❄ permanently interrupted by the...
  • Page 9: Exhaust Gas Ducting

    Exhaust gas ducting It is also possible to operate the Fault-free operation is All parts of the exhaust gas ■ ■ units outdoors or in open spaces guaranteed if the exhaust gas ducting must be reliably without exhaust ducting. ducting is fitted in a rising fastened Its diameter must However, we recommend fitting arrangement and with a vertical...
  • Page 10: Before Commissioning

    REMKO CLK SERIES Before commissioning The units should be checked for The connection hose must not Air distribution ■ visible defects on the operating be subject to torsional forces! and safety devices as well as The fan-assisted heater must not The units are equipped with a ■...
  • Page 11: Commissioning

    Commissioning There should be no kinks or A person, who has been ■ Control panel bends in the hose lines in order adequately trained in the handling to prevent hot-spots forming. of the units, must be tasked with Membrane hoses must not be operation and monitoring of the twisted units.
  • Page 12: Shutdown

    REMKO CLK SERIES Shutdown Heating with room thermostat Ventilation (Accessories) 1. Move the operating In this switch position, the supply switch to the "0" (off) The units operate fully air fan runs permanently. position. automatically and according to the The units can be used for air room temperature.
  • Page 13: Care And Maintenance

    Care and maintenance Regular care and observation of Check that the safety devices Cleaning the heat exchanger ■ some basic requirements, once are operating correctly at yearly or after extended times at regular intervals 1. Set the operating switch to the a standstill, will ensure trouble-free Keep the probes for the safety "0"...
  • Page 14 REMKO CLK SERIES Inspection cover 5. Set down the burner and the 5. Slide the flame tube of the fuel filter carefully beside the burner into the burner flange. Always check that the seal unit. Note dimension X in the ■...
  • Page 15: Troubleshooting

    Troubleshooting - The units were not able to cool CAUTION CAUTION down because the electrical If the burner should carry out Before undertaking any work connection was interrupted. on the units, the power plug a fault shut-down once again - Too high an outlet temperature after the start phase, then must be removed from the due to incorrectly implemented...
  • Page 16: Intended Use

    "Certificate of guarantee" to Our units are carefully packed and equipment. REMKO GmbH & Co. KG at the and delivered in stable transport time when the units are purchased packaging and, if applicable, on The units must only be operated and commissioned.
  • Page 17: Electrical Wiring Diagram

    Electrical wiring diagram white white brown orange black blue Multiflex oil pre-heating Optional: For CLK 30/50 and 70. Series: With CLK 120/150 with oil burner fitted ex works. Legend: = Start-up capacitor = Reset button (burner) H1 = Operating lamp (green) STB = Safety temperature limiter H2 = External burner fault lamp (red) TR = Temperature controller...
  • Page 18: Exploded View Of The Unit

    REMKO CLK SERIES Exploded view of the unit STB probe TW probe TR probe 70 71 Fig. CLK 70 REMKO Multiflex oil REMKO oil filter, preheating standard up to CLK 70 with oil Standard with CLK 120/150 burner fitted ex works.
  • Page 19: Spare Parts List

    Spare parts list Designation CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 EDP no. EDP no. EDP no. EDP no. EDP no. Cover panel 1104703 1104703 1104740 1104770 1104770 Insulation, top 1104704 1104704 1104741 1104771 1104771 Insulation, right 1104705 1104705 1104742...
  • Page 20: Commissioning Of Forced-Air Oil Burners

    REMKO CLK SERIES Commissioning of forced-air oil burners Preparatory tasks Adjusting the ignition electrode and baffle plate CAUTION The commissioning of the forced-air oil burner may only be carried out by trained specialists. After loosening the 4 fastening bolts the mounting baseplate M is pulled off the housing G.
  • Page 21 Adjusting the secondary air Air flap Setting the pump pressure (Nozzle fitting adjustment) The pump pressure should be adjusted, and checked if necessary, during burner commissioning and during all maintenance work. NOTE Never let the pump run for extended periods without any fuel.
  • Page 22: Maintenance Log

    REMKO CLK SERIES ✍ Maintenance log Unit type: ........Unit number: ........10 11 12 13 14 15 16 17 18 19 20 Unit cleaned - outside - Unit cleaned - inside - Fan blade cleaned Combustion chamber cleaned Heat exchanger cleaned...
  • Page 23: Technical Data

    Technical data Unit type CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 Nominal heat load max Nominal heat capacity 26.5 Minimum heat capacity N.A. N.A. N.A. N.A. N.A. Room heating emissions N.A. N.A. N.A. mg/kWh Nominal flow rate 1,760 3,050 4,920...
  • Page 24 REMKO CLK SERIES Unit type CLK 30 CLK 50 CLK 70 CLK 120 CLK 150 Air outlet Ø Flue gas connection ø Dimensions: Length 1,450 1,450 1,610 2,100 2,100 Width Height 1,000 1,000 1,120 1,350 1,350 Weight without blower oil burner...
  • Page 25 Notes...
  • Page 26 REMKO CLK SERIES...
  • Page 28 REMKO QUALITY WITH SYSTEMS Air-Conditioning | Heating | New Energies REMKO GmbH & Co. KG Telephone +49 (0) 5232 606-0 Hotline within Germany Klima- und Wärmetechnik Telefax +49 (0) 5232 606-260 +49 (0) 5232 6 06-0 Im Seelenkamp 12 E-mail info@remko.de...