Table 4: Communication parameters
C P menu
Designation
U n
Communication unit
P r
Communication protocol
The following values are automatically set with
the 'A P' setting: b d = 96, S t = I n
A d
Modbus address
(station address)
b d
Baud rate
S t
Stop and parity bits
t I
Timeout
Fig. 6: Bus connecting cable with 3-pin round connector (order no. 1380-2689)
EB 5724-8 EN
Setting
o F
Bluetooth module not active
b L
Bluetooth module active
r 4
RS-485 module active
S P
SSP
o d
Modbus-RTU slave
A P
Automatic protocol detection
01 to .99
01 to 99
00. to 99.
100 to 199
0.0. to 4.7.
200 to 247
I 2
1200
24
2400
48
4800
96
9600
I 9
19200
38
38400
I n
1 stop bit, no parity
I E
1 stop bit, even parity
I o
1 stop bit, odd parity
2 n
2 stop bits, no parity
0 to 99
With t = 0 min, timeout is deactivated.
After the adjusted time has elapsed, the
electric actuator returns to closed-loop oper-
ation. Serves as bus failure monitoring.
White
Brown
Green
Yellow
Black