Samson TROVIS 5724-8 Mounting And Operating Instructions page 42

Electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

Appendix
CO/PA
Function/
designation
C1.2/C2.2
Source
C1.SP/C2.2 Set point
C1.SP.DIF/
Set point offset
C2.SP.DIF
C1.SP.MIN/
Lower adjustment limit
C1.SP.MIN
C1.SP.MAX/
Upper adjustment limit
C2.SP.MAX
Formula parameters for set point
C1.e/C2.e
Factor AI1
C1.f/C2.f
Factor AI2
C1.g/C2.g
Factor AI3
C1.h/C2.h
Factor AI4
Set point deviation
C1.3/C2.3
Function
PID controller
C1.KP/
Proportional-action coeffi-
C2.KP
cient
C1.TN/
Reset time
C2.TN
C1.TV/
Derivative-action time
C2.TV
C1.Y0/
Operating point
C2.Y0
42
Setting/
adjustment range
7: Set point = Output of controller [2]
8: Set point = Program controller
9: Set point = Program controller +
C1.SP + C1.e * AI1 + C1.f * AI2 + C1.g * AI3 + C1.h * AI4
–50.0 to +150.0 °C
–50.0 to +150.0 °C
–50 to +150 °C
–50 to +150 °C
–9.0 to +99.0
–9.0 to +99.0
–9.0 to +99.0
–9.0 to +99.0
0: Not inverted
1: Inverted by DI1
2: Inverted by DI2
3: Inverted by DI3
4: Inverted by DI4
5: Inverted by LIM1
6: Inverted by LIM2
7: Inverted
0.1 to 999.9
0 to 999 s
0 to 999 s
0.0 to 100.0 %
EB 5724-8 EN