Samson TROVIS 5724-8 Mounting And Operating Instructions page 43

Electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

CO/PA
Function/
designation
Manipulated variable
C1.4/C2.4
Function
C1.YP/C2.
Fixed actuator positioning
YP
value
M ...
Actuator
Actuator parameters
MY.EA
End position guiding (stem
extends)
MY.EE
End position guiding (stem
retracts)
MY.TE
Idle time during end
position guiding
MY.TZ
Dead band (switching
range)
Signal failure
A7.1
Function
A7.YP.ERR
Fixed actuator positioning
value
Actuator
A8.1
Zero calibration
A8.2
Restart conditions
A8.3
Blocking protection
EB 5724-8 EN
Setting/
adjustment range
0:
Controller positioning value
1:
Fixed actuator positioning value with DI1
2:
Fixed actuator positioning value with DI2
3:
Fixed actuator positioning value with DI3
4:
Fixed actuator positioning value with DI4
5:
Fixed actuator positioning value with LIM1
6:
Fixed actuator positioning value with LIM2
0.0 to 100.0 %
0.0 to 49.9 %
50.0 to 100.0 %
0 to 99 s
0.5 to 5.0 %
0:
Last travel value
1:
Fixed positioning value
0.0 to 100.0 %
0:
Extend actuator stem
1:
Retract actuator stem
0:
Start with last operating state
1:
Start with operating function [O]
2:
Start with operating function [I]
0:
No
1:
Yes