Default Disturbance Recorder Settings - ABB RELION 615 Series Applications Manual

Line differential protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC807603-MB A
3.4.2.2
RED615 ANSI
Application Manual
LED
Default usage
8
Protection communication
supervision alarm
9
Supervision alarm
10
Circuit breaker monitoring
alarm
11
-

Default disturbance recorder settings

Table 19:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
U1
6
U2
7
U3
8
-
9
-
10
-
11
-
12
-
Table 20:
Default disturbance recorder binary channels
Channel
ID text
1
LNPLDF1 - pickup
2
LNPLDF1 - trip
3
PHIPTOC1 - pickup
4
DPHHPDOC1 - pickup
5
DPHLPDOC1 - pickup
6
DPHLPDOC2 - pickup
7
NSPTOC1 - pickup
8
NSPTOC2 - pickup
9
INRPHAR1 - blk2h
10
EFHPTOC1 - pickup
Table continues on next page
RED615 standard configurations
ID
LED_ProtectionCommFailure_
1
LED_Supervision_1
LED_CBConditionMonitoring_
1
-
Section 3
Label description
Protection comm. failure
Supervision
CB condition monitoring
-
Level trigger mode
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
69