Functional Diagrams For Other Functions; Functional Diagrams For Other Timer Logics - ABB RELION 615 Series Applications Manual

Line differential protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
RED615 standard configurations
3.3.3.7
3.3.3.8
LNPLDF_LS_TRIP
LNPLDF_HS_TRIP
LNPLDF1_87L-1_PROT_NOT_ACTIVE
PCSITPC1_PCS-1_ALARM
GUID-98839EBE-D2D0-46E0-A765-E3720BB1BFE2 V1 EN
Figure 65:
Timer logic for differential trip and communication not active
64

Functional diagrams for other functions

NOT
IN
O:11|T:2.5|I:6
NOT
IN
TRUE
O:12|T:2.5|I:5
Control
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
O:13|T:2.5|I:0
GUID-5ECF83A7-9FFC-4308-A4EF-807EBC0259F2 V1 EN
Figure 64:
Functions for general logic states TRUE and FALSE, protection setting
group selection and local and remote control
Other functions include generic function blocks which are related to the relay only, for
example, local/remote switch, some generic functions related to logic TRUE or FALSE,
push button logic (valid for certain relay types) and so on.

Functional diagrams for other timer logics

The configuration also includes line differential trip, inactive communication and backup
protection trip logic. The trip logics are connected to minimum pulse timer TPGAPC1 for
setting the minimum pulse length for the outputs. The output from TPGAPC1 is connected
to the binary outputs.
OR
B1
O
B2
O:120|T:2.5|I:6
OR
B1
O
B2
O:121|T:2.5|I:13
OUT
TRUE
OUT
FALSE
OFF
LOCAL
CONTROL_LOCAL
STATION
REMOTE
CONTROL_REMOTE
ALL
BEH_TEST
BEH_BLK
TPGAPC1
IN1
OUT1
IN2
OUT2
O:122|T:2.5|I:1
1MAC807603-MB A
Protection
BI_SG_2
SG_LOGIC_SEL
BI_SG_3
SG_1_ACT
BI_SG_4
SG_2_ACT
BI_SG_5
SG_3_ACT
BI_SG_6
SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
O:141|T:2.5|I:0
DIFFERENTIAL_TRIP_PULSE
LNPLDF_NOT_ACTIVE_OR_PCSRTPC_ALARM
RED615 ANSI
Application Manual