Functional Diagrams - ABB RELION 615 Series Applications Manual

Line differential protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC807603-MB A
3.4.3
RED615 ANSI
Application Manual
Channel
ID text
47
PHPTUV - trip
48
-
49
INRPHAR1 - blk2h
50
PCSITPC1 - alarm
51
CCSPVC1 - alarm
52
-
53
X110BI3 - CB open
54
X110BI4 - CB closed
55
DARREC1 - unsuc recl/close CB
56
DARREC1 - inpro
57
General pickup pulse
58
General trip pulse
59
-
60
-
61
-
62
-
63
-
64
-

Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-to-
function connections. The default connections can be viewed and changed with PCM600
according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
protection relay's standard configuration. However, the 12 analog channels available for
the disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The phase currents to the protection relay are fed from Rogowski or Combi sensors. The
residual current to the protection relay is fed from either residually connected CTs, an
external core balance CT, neutral CT or calculated internally.
The phase voltages to the protection relay are fed from Combi sensors. The residual
voltage is calculated internally.
The signal marked with IA, IB and IC represents the three phase currents. The signal IG
represents the measured ground current.
RED615 standard configurations
Section 3
Level trigger mode
Level trigger off
-
Level trigger off
Level trigger off
Level trigger off
-
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
-
-
-
-
-
-
71