4 Configuration

4.1

Overview

Installation
Reading and writing parameters
Changing the setting
See also
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual, 06/2019, L1V30499596021-01
Information about installation of the necessary components is to be found in the relevant
operating instructions. You will find more information on this in chapter Reference
documents (Page 7).
It is always possible to read parameters with the powerconfig software (front interface or
fieldbus interface), irrespective of whether the switch is set to "Local bus ON" (local) or
"Local bus OFF" (remote).
For writing parameters and switching, the switch must be set to "Local" or "Remote".
⇒ with the ETU display of the circuit breaker (
)
ON/OFF
If the circuit breaker is set to "Local bus ON" (local):
● Writing and switching parameters can only be performed via the front interface via
TD410 / TD420.
● Parameters cannot be written or switched via the fieldbus interface (Modbus TCP or
Modbus RTU). An error message is displayed in powerconfig.
If the circuit breaker is set to "Local bus OFF" (remote):
● Writing and switching parameters can only be performed via the fieldbus interface.
● Parameters cannot be written via the front interface of the circuit breaker and the
TD410 / TD420. An error message is displayed in powerconfig.
Commissioning communication modules (Page 30)
Industry online support (https://support.industry.siemens.com/)
Display → Settings → Modules → Local bus →