Actuation Module For Remote Operation (Com Act) - Siemens SENTRON 3WL10 Manual

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Description
2.1 Communication modules
2.1.3

Actuation module for remote operation (COM ACT)

The COM-ACT module is required to switch the 3WL10 / 3VA27 circuit breaker on or off via
the communication modules.
The COM-ACT module is installed in the accessory area on the right on the front panel of the
circuit breaker and activates the auxiliary solenoids (CC closing coil / ST shunt trip).
The COM ACT module can be used to switch the circuit breaker on or off via the
communication connection and, at the same time, to operate it manually using the magnets.
The COM ACT module is installed as standard when the circuit breaker is ordered for
communication.
Figure 2-3
Technical specifications
Feature
Designation
Article number (as spare part)
Storage temperature
Operating temperature
18
Actuator module COM ACT
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
Value
COM ACT
3VW9011-0AT10
−40 °C ... +70 °C
−25 °C ... +70 °C
System Manual, 06/2019, L1V30499596021-01