Siemens SENTRON 3WL10 Manual

Siemens SENTRON 3WL10 Manual

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:

Advertisement

Manual
SENTRON
Air Circuit Breaker and
Molded Case Circuit Breaker
3WL10 and 3VA27 with communication-capability
Edition
05/2019
siemens.de/SENTRON

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SENTRON 3WL10

  • Page 1 Manual SENTRON Air Circuit Breaker and Molded Case Circuit Breaker 3WL10 and 3VA27 with communication-capability Edition 05/2019 siemens.de/SENTRON...
  • Page 2: L1V30499596021

    Introduction Description SENTRON Commissioning Configuration Protection devices Communication 3WL10 Air Circuit Data structure Breakers & 3VA27 Molded Case Circuit Breakers List of abbreviations System Manual 06/2019 L1V30499596021-01...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Table of contents Introduction ............................. 5 About this documentation ......................5 Product-specific information ..................... 5 Safety instructions ........................5 Reference documents ....................... 7 Advanced training courses ....................... 8 3WL10 / 3VA27 circuit breakers ....................8 1.6.1 System overview ........................8 1.6.2 Software applications ......................
  • Page 5 Table of contents Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 6: Introduction

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens' products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks.
  • Page 7 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer's exposure to cyber threats.
  • Page 8: Reference Documents

    Schalten, Schützen, Verteilen in Niederspannungsnetzen (Switching, Protection and Distri- ISBN 3-89578-041-3 bution in Low-Voltage Networks), substantially extended and revised edition 1997 Siemens: Residual Current Protective Devices, Low-Voltage Circuit Protection Technology E10003-E38-9T-B3011 Primer Siemens AG © 04 / 2009 Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers...
  • Page 9: Advanced Training Courses

    1.5 Advanced training courses Advanced training courses Find out about training courses on offer on the following link. Training for Industry (https://www.siemens.com/sitrain-lowvoltage) This is where you can choose from ● Web-based training courses (online, informative, free) ● Classroom training courses (course attendance, comprehensive, subject to fee).
  • Page 10 Introduction 1.6 3WL10 / 3VA27 circuit breakers Overview ① Position signaling switch of the circuit breaker in the guide frame (COM PSS), not shown in the figure. ② Breaker Connect module, external power supply ③ Module slots for communication modules or digital I/O modules ④...
  • Page 11: Software Applications

    Software applications Energy management with powermanager Siemens offers the powermanager software application, which is designed for power and plant monitoring applications. When used in conjunction with SENTRON protection devices such as 3VA, 3WL, 3VL, and PAC as well as equipment supplied by third parties, powermanager is a power monitoring system that reduces energy costs and increases the availability of electrical supply and distribution systems.
  • Page 12 ● Switching recommendations in the event of limit violations ● Remote control of circuit breakers You can find more information on energy management with powermanager in the Internet (https://new.siemens.com/global/en/products/energy/low-voltage/components/sentron- measuring-devices-and-power-monitoring.html). Commissioning and service powerconfig is a commissioning and service software application for communication-capable measuring devices and circuit breakers from the SENTRON product family.
  • Page 13 Introduction 1.6 3WL10 / 3VA27 circuit breakers Figure 1-1 powerconfig Further information on powerconfig can be found on the Internet (https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10230050). Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 14: Individually Configured Circuit Breakers

    You can assemble your own 3WL10/3VA27 circuit breaker simply and quickly in the online configurator and then generate an article number. Online configurator for 3WL10 (https://mall.industry.siemens.com/spice/pcmplus/app/) Online configurator for 3VA27 (https://mall.industry.siemens.com/spice/pcmplus/app/) In the Online Configurator, impermissible combinations are automatically excluded in the article number.
  • Page 15 Introduction 1.7 Individually configured circuit breakers Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 16: Description

    2 Description Communication modules 2.1.1 COM043 (Modbus TCP) Overview The COM043 module offers fast and simple integration in monitoring, maintenance, and energy management systems as well as in industrial automation systems by way of the Modbus TCP module. Communication permits the continuous transfer of data, such as status and measured values, from the 3WL10 / 3VA27 circuit breaker.
  • Page 17: Com042 (Modbus Rtu)

    Description 2.1 Communication modules Technical specifications Feature Value Designation COM043 Article number in conjunction with 3WL10 / 3VA27 Z option F11 Article number (as spare part) 3VW9011-0AT16 Protocol Modbus TCP Transmission medium Ethernet, IEEE 802.3 Transmission rate 10/100 Mbps Port Connection technology An RJ45 socket Simultaneous TCP clients...
  • Page 18 Description 2.1 Communication modules Default settings Feature Value Transmission rate 19200 bps Address Format Technical specifications Feature Value Designation COM042 Article number in conjunction with 3WL10 / 3VA27 Z option F12 Article number (as spare part) 3VW9011-0AT17 Protocol Modbus RTU Transmission medium RS485 Transmission rate...
  • Page 19: Actuation Module For Remote Operation (Com Act)

    Description 2.1 Communication modules 2.1.3 Actuation module for remote operation (COM ACT) The COM-ACT module is required to switch the 3WL10 / 3VA27 circuit breaker on or off via the communication modules. The COM-ACT module is installed in the accessory area on the right on the front panel of the circuit breaker and activates the auxiliary solenoids (CC closing coil / ST shunt trip).
  • Page 20: Breaker Connect Module

    Description 2.1 Communication modules 2.1.4 Breaker Connect module Two versions are available depending on the primary voltage used: ● Breaker Connect module 110 to 240 V AC/DC (option; can be ordered via Z option) ● Breaker Connect module 24 to 48 V AC/DC (standard) Figure 2-4 Breaker Connect module Via the Breaker Connect module, the electronic trip units (3-series and 6-series ETUs) and...
  • Page 21: Iom040 Digital I/O Module

    Description 2.1 Communication modules 2.1.5 IOM040 digital I/O module The IOM040 digital I/O module provides two input and two output contacts for electrical control and signaling of states, alarms, and tripping of the circuit breaker. Default settings of the inputs and outputs can be selected via the ETU display. The settings can be freely configured via the TD410/TD420 test and commissioning tools and the powerconfig software.
  • Page 22: Iom300 External Digital I/O Module

    Description 2.1 Communication modules 2.1.6 IOM300 external digital I/O module The IOM300 external digital I/O module provides 11 input and 10 output contacts for electrical control and signaling of states, alarms, and tripping of the circuit breaker. The IOM300 external digital I/O module is suitable for external mounting on a standard rail. The IOM300 external digital I/O module is suitable for the ETUs of both the 6-series and the 3-series because it is connected directly to the CB1 and CB2 terminals of the auxiliary conductor terminal system.
  • Page 23: Position Signaling Switch Communication (Pss - Com)

    Description 2.1 Communication modules 2.1.7 Position signaling switch communication (PSS - COM) Via the communication link, the position signaling switch PSS - COM provides the signal indicating whether the circuit breaker in the guide frame is inserted or removed. Unlike the position signaling switch PSS, whose signals are available at the auxiliary conductor terminal strip, the position signaling switch PSS - COM only signals two different states: ●...
  • Page 24: Metering Function Mf Basic And Mf Advanced

    Description 2.2 Metering function MF Basic and MF Advanced Metering function MF Basic and MF Advanced Overview The ETUs of the 6-series can be expanded with the metering functions MF Basic or MF Advanced: ● MF Basic provides many measured values in accordance with IEC-61557-12. ●...
  • Page 25 Description 2.2 Metering function MF Basic and MF Advanced Metering functions of the ETUs of the 6-series Instantaneous values Measured values Precision Reference standard: IEC 61557-12 Currents (rms value) , neutral Ground-fault current Phase-to-phase voltage (rms value) U12, U23, U31 0.5 % Phase-to-neutral voltage (rms value) V U1, U2, U3...
  • Page 26 Description 2.2 Metering function MF Basic and MF Advanced Instantaneous values Information on tripping and switch-off data Protection functions Type of protection function tripped e.g. L, S, I, G, U Fault values per phase A / V / e.g. Hz w / , neutral for protection S Time stamp Date, time, and consecutive number...
  • Page 27: Dsp800 Display

    Description 2.3 DSP800 display Technical specifications Feature Value Designation Metering function Basic Article number in conjunction with 3WL10 / 3VA27 See ETU650/ETU660 Article number (as spare part) 3VW9011-0AT01 Storage temperature −40 °C … +70 °C Operating temperature −25 °C … +70 °C DSP800 display The DSP800 display is used for the visualization of circuit breakers directly at the control cabinet door.
  • Page 28 Description 2.3 DSP800 display Technical specifications Feature Value Designation DSP800 Article number (as spare part) 3VA9987-0TD10 Protocol Modbus TCP Transmission medium Ethernet, IEEE 802.3 Transmission rate 100 Mbps Connection technology One RJ-45 socket Total circuit breakers Max. 8 3VA molded case circuit breakers Max.
  • Page 29 Description 2.3 DSP800 display Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 30: Commissioning

    3 Commissioning Overview Overview The Breaker Connect module is a prerequisite for communication operation. The Breaker Connect module is installed as standard when the circuit breaker is ordered for communication. Figure 3-1 3WL10 / 3VA27 fixed breaker, "plug-and-play" installation – Breaker Connect module plus two modules The COM042 module and COM043 module can simply be plugged into the slot provided in the auxiliary conductor contact system.
  • Page 31: Commissioning Communication Modules

    Commissioning 3.2 Commissioning communication modules See also System overview (Page 8) Commissioning communication modules The COM modules must be enabled either on the ETU display or in the powerconfig software. ⇒ with ETU display ( Display → Settings → Modules → Local bus → ON Setup via local laptop / Ethernet ⇒...
  • Page 32 ● With a ping command (Windows search bar, call cmd.exe, enter ping and IP addressed), test whether communication with the device is available. See also Information/Download powerconfig (https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10230050) Getting Started powerconfig (https://support.industry.siemens.com/cs/ww/en/view/109480256) Download powerconfig (http://support.automation.siemens.com/WW/view/en/63452759) Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 33 Commissioning 3.2 Commissioning communication modules Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 34: Configuration

    ● Parameters cannot be written via the front interface of the circuit breaker and the TD410 / TD420. An error message is displayed in powerconfig. See also Commissioning communication modules (Page 30) Industry online support (https://support.industry.siemens.com/) Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 35: Configuring The Communication Function

    3D drawings, Eplan macros, etc. You will find more information on this in the Internet: Online configurator for 3WL10 (https://mall.industry.siemens.com/spice/pcmplus/app/) Online configurator for 3VA27 (https://mall.industry.siemens.com/spice/pcmplus/app/) Figure 4-1 Online configurator – Example view Communication 3WL10 Air Circuit Breakers &...
  • Page 36: Data Structure

    5 Data structure Units of information such as status information or measured variables are made available in suitable data formats by products in the SENTRON range. Modbus data formats and byte ordering Identifying data points Abbreviation Description 8-bit unsigned 16-bit unsigned 32-bit unsigned U32SWAPPED 32-bit unsigned with reversed register order...
  • Page 37: Floating-Point Number According To Ieee 754

    Data structure 5.2 Floating-point number according to IEEE 754 Floating-point number according to IEEE 754 Float32 (FP32) and Float64 (FP64) are stored in accordance with the following tables: Representation of the 32-bit floating-point number (single precision) in accordance with IEEE 754 0 …...
  • Page 38: Register Addresses

    Data structure 5.3 Register addresses Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0002 Current L1 429496729.5 FP32 0x0004 Current L2 429496729.5 FP32 0x0006 Current L3 429496729.5 FP32 0x0008 Neutral con- 429496729.5 FP32 ductor current 0x000A Calculated 429496729.5...
  • Page 39 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x003C Apparent pow- −214748364.8 214748364.7 FP32 0x003E Total apparent −214748364.8 214748364.7 FP32 power 0x0040 Reactive pow- −214748364.8 214748364.7 FP32 0x0042 Reactive pow- −214748364.8 214748364.7 FP32 0x0044 Reactive pow-...
  • Page 40 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FA0 Commands – R/W First register: Command (value 0 … 27) Second register: Parameter (must be zero, expect com- mand 27) 0: Dummy command 1: Reset trip 2: Rest signals 3: RESET STATISTICAL COM...
  • Page 41 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FC8 Status – – Bit 0: Circuit breaker closed Global 1 Bit 1: Circuit breaker position connected Bit 2: Circuit breakers discon- nected / ETU active Bit 3: Circuit breaker tripped Bit 4: Circuit breaker ready to close...
  • Page 42 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FCC Status – – Bit 0: Parameter assignment via flags 1 Bit 2: Test running Bit 3: Test device (TD) is con- nected Bit 4: LED mode active Bit 5: Parameter set in use Bit 6: ETU supply via auxiliary...
  • Page 43 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FD1 Status – – Bit 0: Underfrequency (fu) ac- timing 2 tive Bit 1: Overfrequency (fo) active Bit 2: Voltage unbalance protec- tion active 0x0FD2 Status –...
  • Page 44 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FD5 Status – – Bit 0: Overload (LT) pre-alarm warnings, Bit 1: Ground fault (GF) pre- alarms 1 alarm Bit 2: In_pal (1) warning Bit 3: Ground fault feedback (Gret) pre-alarm Bit 6: Internal CB bus error...
  • Page 45 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FD6 Status – – Bit 0: Overtemperature (T) warnings, alarm alarms 2 Bit 1: Only overtemperature (T) alarm Bit 2: Only current unbalance (I-NBA) alarm Bit 4: Only reverse power (RP) alarm...
  • Page 46 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FD8 Status – – Bit 3: Battery charge low warnings, Bit 8: Metering function (MF) alarms 4 installation warning Bit 13: Metering function (MF) error Bit 14: Only DST –...
  • Page 47 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x0FDF Status – – Bit 0: Output 101 Ext I/O module Bit 1: Output 102 IOM300 Bit 2: Output 103 output A Bit 3: Output 104 Bit 4: Output 105 Bit 5: Output 106 Bit 6: Output 107...
  • Page 48 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x1052 Maximum – 0: N/A current value 1: L1 Phase 2: L2 3: L3 4: N 0x1053 Time stamp of 4294967295 U32SWAPPED maximum current in seconds 0x1055...
  • Page 49 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x10DA Energy storage 4294967295 U32SWAPPED time 0x1197 Displays – – – – Bit 0: Type of installation Bit 1: Reversed pole arrange- ment 0x1198 Rated current 6300...
  • Page 50 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x1226 Rated voltage – R/W 0: 0 V Un (V) 1: 115 V 2: 120 V 3: 190 V 4: 208 V 5: 220 V 6: 230 V 7: 240 V 8: 277 V...
  • Page 51 Data structure 5.3 Register addresses Register Number Name Unit Min. Max. Fac- Description address of regis- ters 0x1593 Function – R/W 0: – selection 1: Overload protection (LT) pre- I/O module alarm IM040 2: Overload protection (LT) 2. Output active 3: ST overload protection (LT) active 4: Overload protection (LT) trip...
  • Page 52: A List Of Abbreviations

    A List of abbreviations Overview Table A- 1 Meaning of abbreviations used in this document Abbreviation Meaning AC voltage Actuator module Closing coil Direct voltage Deutsches Institut für Normierung e. V. (German Institute for Standardization) European Standard Electronic trip unit Ground fault (ground-fault protection GF) Ground fault (ground-fault protection) Instantaneous (instantaneous short-circuit protection INST)
  • Page 53 List of abbreviations Abbreviation Meaning Verein Deutscher Ingenieure (Association of German Electrical Engineers) Verein Deutscher Ingenieure (Association of German Engineers) Table A- 2 Meaning of symbols and abbreviations Symbol/ Meaning abbreviation Inrush current " Initial balanced short-circuit current Let-through energy Making capacity;...
  • Page 54 List of abbreviations Symbol/ Meaning abbreviation Trip time; delay time; time-lag class Trip time associated with current setting value of adjustable overload protection Trip time associated with short-time delayed tripping current; delay time of S pro- tection Voltage across main contacts of the molded case circuit breaker Maximum voltage;...
  • Page 55 List of abbreviations Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers System Manual, 06/2019, L1V30499596021-01...
  • Page 56: Index

    Index Bit count, 35 Energy management Breaker Connect module powermanager, 10 Functions, 19 Mounting, 29 Technical data with Z option F26, 19 Technical specifications, 19 Fault rectification, 31 Versions, 19 Floating-point number, 36 Circuit breaker IOM040 Creating with powerconfig, 30 Functions, 20 Online configurator, 34 Technical specifications, 20...
  • Page 57 Index Remote control, 18 Spare parts, 13 System time, 36 Technical specifications Breaker Connect module, 19 COM ACT, 18 COM RTC, 22 COM042, 17 COM043, 16 DSP800 display, 27 IOM040, 20 IOM300, 21 Metering function MF Basic and MF Advanced, 26 PSS-COM, 22 Time stamp, 36 Training, 8, 8...