Commissioning Communication Modules - Siemens SENTRON 3WL10 Manual

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Commissioning

3.2 Commissioning communication modules

See also
System overview (Page 8)
3.2
Commissioning communication modules
The COM modules must be enabled either on the ETU display or in the powerconfig
software.
⇒ with ETU display (
Setup via local laptop / Ethernet
⇒ Windows OS:
To be able to connect to the COM module, you may have to change the network address of
your PC/notebook when you commission the COM module for the first time.
● Address area: 169.254.x.x (Auto-IP)
● Subnet: 255.255.0.0
Consult your network administrator for more information.
Searching for and creating circuit breaker 3WL10/3VA27 with powerconfig
1. In powerconfig, click "Search".
2. Change to "Extended IP search".
3. In
4. Click "Search"
The found devices are listed.
30
Display → Settings → Modules → Local bus → ON
Control Panel → Network and Sharing Center → Change adapter settings
, enter the IP address of 3WL10/3VA27.
.
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
)
System Manual, 06/2019, L1V30499596021-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 3va27

Table of Contents