Siemens SENTRON 3WL10 Manual page 51

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Data structure
5.3 Register addresses
Register
Number
Name
address
of regis-
ters
0x1593
1
Function
selection
I/O module
IM040
2. Output
0x258B
1
Module status
0x25A7
1
Module status
50
Unit Min.
Max.
0
15
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
Fac-
Ac-
Description
tor
ces
s
1
R/W 0: –
1: Overload protection (LT) pre-
alarm
2: Overload protection (LT)
active
3: ST overload protection (LT)
active
4: Overload protection (LT) trip
5: Short-time-delayed short-
circuit protection (ST) tripped
6: Instantaneous short-circuit
protection (INST) tripped
7: Ground-fault (GF) tripped
8: Every trip operation
9: Every alarm
10: Ir_pal (1)
11: Ir_pal (2)
12: Circuit breaker open
13: Circuit breaker closed
14: CB bus not active
15: –
R
Bit 0: CRC error
Bit 1: CRC calculated
R
Bit 0: CRC
Bit 1: CRC calculated
Bit 2: Ethernet connection sta-
tus error
Bit 3: SNTP server error
Bit 4: SNTP server not syn-
chronized
System Manual, 06/2019, L1V30499596021-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 3va27

Table of Contents