Siemens SENTRON 3WL10 Manual page 42

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Register
Number
Name
address
of regis-
ters
0x0FCC
1
Status
flags 1
0x0FCE
1
Status
Accessories 1
0x0FCF
1
Status
Accessories 2
0x0FD0
1
Status
timing 1
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual, 06/2019, L1V30499596021-01
Unit Min.
Max.
0
0
0
0
0
0
0
0
5.3 Register addresses
Fac-
Ac-
Description
tor
ces
s
R
Bit 0: Parameter assignment via
Bit 2: Test running
Bit 3: Test device (TD) is con-
nected
Bit 4: LED mode active
Bit 5: Parameter set in use
Bit 6: ETU supply via auxiliary
voltage
Bit 7: ETU supply via test de-
vice (TD)
Bit 8: ETU supply via metering
function (MF advanced)
Bit 9: ETU firmware
Bit 10: Parameterization
R
Bit 0: I/O module IOM040
Bit 1: I/O module IOM040-2
Bit 4: COM Modbus RS 485
Bit 5: COM PROFIBUS
Bit 6: COM043 (Modbus TCP)
Bit 12: COM PROFINET
Bit 13: Reserved
R
Bit 0: Ext I/O module - IOM300
Bit 9: Reserved
R
Bit 0: Overload (LT) active
Bit 1: Short-time-delayed short-
circuit protection (ST) active
Bit 2: Ground-fault protection
(GF) active
Bit 4: Current unbalance protec-
tion (I-NBA) active
Bit 5: Normal directional protec-
tion active
Bit 6: Reverse directional pro-
tection active
Bit 9: Undervoltage protection
(Uu) active
Bit 10: Overvoltage protection
(Uo) active
Bit 12: Ground fault feedback
(Gret) active
Bit 13: Directional short-circuit
protection active
Bit 15: Reverse power active
Data structure
41