Siemens SENTRON 3WL10 Manual page 50

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Register
Number
Name
address
of regis-
ters
0x1226
1
Rated voltage
Un (V)
0x1591
1
Function
selection
I/O module
IM040
1. Output
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual, 06/2019, L1V30499596021-01
Unit Min.
Max.
0
19
0
15
5.3 Register addresses
Fac-
Ac-
Description
tor
ces
s
1
R/W 0: 0 V
1: 115 V
2: 120 V
3: 190 V
4: 208 V
5: 220 V
6: 230 V
7: 240 V
8: 277 V
9: 347 V
10: 380 V
11: 400 V
12: 415 V
13: 440 V
14: 480 V
15: 500 V
16: 550 V
17: 600 V
18: 660 V
19: 690 V
1
R/W 0: –
1: Overload protection (LT) pre-
alarm
2: Overload protection (LT)
active
3: ST overload protection (LT)
active
4: Overload protection (LT)
tripped
5: Short-time-delayed short-
circuit protection (ST) tripped
6: Instantaneous (INST) tripped
7: Ground-fault (GF) tripped
8: Every trip operation
9: Every alarm
10: Ir_pal (1)
11: Ir_pal(2)
12: Circuit breaker open
13: Circuit breaker closed
14: CB bus not active
15: –
Data structure
49