5.3

Register addresses

Register
Number
Name
address
of regis-
ters
0x0002
2
Current L1
0x0004
2
Current L2
0x0006
2
Current L3
0x0008
2
Neutral con-
ductor current
0x000A
2
Calculated
ground-fault
current
0x0016
1
Phase with the
highest current
0x0018
2
Maximum
phase current
0x001A
2
Voltage
L1-N
0x001C
2
Voltage
L2-N
0x001E
2
Voltage
L3-N
0x0020
2
Voltage
L1-L2
0x0022
2
Voltage
L2-L3
0x0024
2
Voltage
L3-L1
0x002E
2
Frequency
0x0030
2
Active power
L1
0x0032
2
Active power
L2
0x0034
2
Active power
L3
0x0036
2
Total active
power
0x0038
2
Apparent pow-
er
L1
0x003A
2
Apparent pow-
er
L2
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual, 06/2019, L1V30499596021-01
Unit Min.
Max.
A
0
429496729.5
A
0
429496729.5
A
0
429496729.5
A
0
429496729.5
A
0
429496729.5
0
4
A
0
429496729.5
V
0
6553.5
V
0
6553.5
V
0
6553.5
V
0
6553.5
V
0
6553.5
V
0
6553.5
Hz
30.00
80.00
W
−214748364.8 214748364.7
W
−214748364.8 214748364.7
W
−214748364.8 214748364.7
W
−214748364.8 214748364.7
VA
−214748364.8 214748364.7
VA
−214748364.8 214748364.7
5.3 Register addresses
Fac-
Ac-
Description
tor
ces
s
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
0: N/A
1: L1
2: L2
3: L3
4: N
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
1
R
FP32
Data structure