Siemens SENTRON 3WL10 Manual page 46

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Register
Number
Name
address
of regis-
ters
0x0FD8
1
Status
warnings,
alarms 4
0x0FD9
1
Status
warnings,
alarms 5
0x0FDC
1
Status
Ext I/O module
IOM300
Input A
0x0FDE
1
Status
I/O module
IOM040
input
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual, 06/2019, L1V30499596021-01
Unit Min.
Max.
0
0
0
0
0
0
0
0
5.3 Register addresses
Fac-
Ac-
Description
tor
ces
s
R
Bit 3: Battery charge low
Bit 8: Metering function (MF)
installation warning
Bit 13: Metering function (MF)
error
Bit 14: Only DST – forward
(FW) alarm
Bit 15: Only DST – backward
(BW) alarm
R
Bit 0: Time and date not syn-
chronized
Bit 1: CB bus modules installa-
tion error
Bit 2: Error in configuration
Bit 3: Maintenance warning
Bit 5: CB undefined
Bit 6: SNTP synchronization
warning
Bit 7: Reserved
Bit 8: Module memory alarm
Bit 10: ETU module connection
warning
Bit 11: Arc suppression (DAS)
active
Bit 12: ETU monitoring alarm 1
Bit 13: ETU monitoring alarm 2
R
Bit 0: Input 101
Bit 1: Input 102
Bit 2: Input 103
Bit 3: Input 104
Bit 4: Input 105
Bit 5: Input 106
Bit 6: Input 107
Bit 7: Input 108
Bit 8: Input 109
Bit 9: Input 110
Bit 10: Input 111
R
Bit 0: Input 11
Bit 1: Input 12
Data structure
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 3va27

Table of Contents