Description
2.1 Communication modules
2.1.7

Position signaling switch communication (PSS - COM)

Via the communication link, the position signaling switch PSS - COM provides the signal
indicating whether the circuit breaker in the guide frame is inserted or removed.
Unlike the position signaling switch PSS, whose signals are available at the auxiliary
conductor terminal strip, the position signaling switch PSS - COM only signals two different
states:
● "INSERTED" breaker position (circuit breaker in the CONNECT position)
● "ISOLATED" breaker position (circuit breaker in the TEST or DISCONNECT position)
The PSS - COM position signaling switch is installed as standard if the withdrawable circuit
breaker is ordered for communication.
Technical specifications
Feature
Designation
Article number (as spare part)
Storage temperature
Operating temperature
2.1.8

Ready-to-close signaling switch for communication (COM RTC)

The COM RTC module ascertains the ready-to-close state and transmits this information to
the communication system. The function is the same as that of the RTC ready-to-close
signaling switch.
The COM RTC module and the RTC ready-to-close signaling switch function can be
operated simultaneously.
The COM RTC module is installed as standard when the circuit breaker is ordered for
communication.
Technical specifications
Feature
Designation
Article number (as spare part)
Storage temperature
Operating temperature
22
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
Value
PSS - COM
3VW9011-0AT12
−40 °C ... +70 °C
−25 °C ... +70 °C
Value
COM RTC
3VW9011-0AT11
−40 °C ... +70 °C
-25 °C ... +70 °C