Siemens SENTRON 3WL10 Manual page 41

Air circuit breakers & molded case circuit breakers
Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Data structure
5.3 Register addresses
Register
Number
Name
address
of regis-
ters
0x0FC8
1
Status
Global 1
0x0FCA
1
Status
Glitch 1
40
Unit Min.
Max.
0
0
0
0
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
Fac-
Ac-
Description
tor
ces
s
R
Bit 0: Circuit breaker closed
Bit 1: Circuit breaker position
connected
Bit 2: Circuit breakers discon-
nected / ETU active
Bit 3: Circuit breaker tripped
Bit 4: Circuit breaker ready to
close
Bit 5: Circuit breaker in unde-
fined condition
Bit 6: Circuit breaker open
Bit 7: Error on tripping
Bit 8: Local/remote control
Bit 9: Warning active
Bit 10: Alarm active
Bit 11: Protective function active
Bit 12: Circuit breaker tripped
Bit 13: Position in guide frame
undefined
Bit 14: Reserved
Bit 15: ETU communication
R
Bit 0: Parameter changed
Bit 1: Trip reset
Bit 2: Reset
Bit 4: Open command
Bit 5: Close command
Bit 10: Update measurement
history
Bit 11: Reset signaling
Bit 12: Energy reset
Bit 13: Switch over parameter
set
Bit 14: New event
System Manual, 06/2019, L1V30499596021-01