Data structure
5.3 Register addresses
Register
Number
Name
address
of regis-
ters
0x10DA
2
Energy storage
time
0x1197
1
Displays
0x1198
1
Rated current
In (A)
0x119A
8
Serial number
of the circuit
breaker
0x11A2
8
Article number
0x11AA
1
Number of
poles
0x11B5
1
Rating N-
conductor
0x11B6
1
Line frequency
0x11B7
1
Tripping
characteristic
0x11D0
1
Metering
module
0x1214
5
Plant identifier
0x1219
5
Location
identifier
0x1224
1
External
current
transformer
48
Unit Min.
Max.
s
0
4294967295
A
100
6300
1
3
0
3
0
1
0
2
0
2
0
2
Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
Fac-
Ac-
Description
tor
ces
s
1
R
U32SWAPPED
R
Bit 0: Type of installation
Bit 1: Reversed pole arrange-
ment
1
R
U16
R
U8[16]
R
U8[16]
1
R
U16
1
R
0: 50 %
1: 100 %
2: 150 %
3: 200 %
1
R
0: 50Hz
1: 60Hz
1
R
0: LI
1: LSI
2: LSIG
1
R
0: N/A
1: Metering function (MF Basic)
2: Metering function (MF Ad-
vanced)
R/W U8[10]
R/W U8[10]
1
R/W 0: Not installed
1: Star-point current transformer
(Gret_CT)
2: Summation current trans-
former (Rc)
System Manual, 06/2019, L1V30499596021-01