Configuration Of The Serial Interfaces - JUMO LOGOSCREEN nt Interface Description

Paperless recorder with tft display and compactflash card
Hide thumbs Also See for LOGOSCREEN nt:
Table of Contents

Advertisement

3 Connecting the interface

3.4 Configuration of the serial interfaces

Configuration
on the
paperless
recorder
Configuration
through setup
program
Interface type
Protocol
Baud rate
Transmission mode
(RTU)
Device address
Min. response time
12
On the recorder, select Configuration
!
General.
The parameters for the configuration of the interface will now be available.
Configuration with the aid of the setup software is made through the menu
item Edit
Interface.
Parameter
Type
Protocol
Baud rate
Data format
Device address
Min. response time
For communication via the back panel RS232 interface and the
setup interface, the device address must be observed, even
though it is not a bus interface!
The configuration of the setup interface cannot be edited,
but is fixed to
- Modbus slave,
- 9600 bps,
- 8-1-none,
- device address 1
The three serial interfaces can be operated simultaneously. There
are merely some interlocks built in at the protocol level (e.g. only
one setup can be written at a time).
!
Interface
Value/Selection
RS232,
RS485
Modbus slave,
Modbus master,
bar code
9600 bps,
19200 bps,
38400 bps
8-1-none,
8-1-odd,
8-1-even
1 — 254
0 — 500msec
!
Interface 1/2
Description
Can only be edited for
interface 1.
See Chapter 3.3 Switching
between RS232 and
RS485, page 11
see
Chapter 5 Serial
protocol types, page 33.
see Chapter 4.3 Timing
sequence for
communication, page 16.
see Chapter 4.2
Transmission mode (RTU),
page 15.
see Chapter 4.5 Device
address, page 18.
see Chapter 4.3 Timing
sequence for
communication, page 16.