2.9 Fine setting of the preset illumination levels
If certain zones are illuminated too strongly or not enough, fine settings can be carried out individually for each zone.
Please note, however, that these fine settings are only possible to a limited degree.
Example: If the lux meter in Zone 3 indicates insufficient illumination and if it needs to be increased, proceed as
follows: Press the "Lock/Unlock" button; the green LED switches on. Then press "Lux" and "3" to select Zone 3.
Press and hold the "Dim +" button, the green LED flashes as long as the button is pressed and the illumination in
Zone 3 increases. Finally, press "Lock/Unlock" again; the green LED switches off.
Note: The detector works on the basis of the effective daylight recording at the end of the programming process
with "Lock/Unlock". Up to 2 minutes may pass until the change is adopted and the lighting is reset.
2.10 Time settings (4)
The following timers are available:
Time 1 (delay)
Time 4 (standby-light)
The times are set as follows:
1. Briefly press "Lock/Unlock" button: Programming mode
2. Briefly press "Time" button
3. Press button for "time"
"1"
"4"
4. Select desired time 5 min - 60 min (standby-light also possible without limits "∞")
5. Briefly press "Lock/Unlock" button: Operating mode
2.11 Switch off standby-light and set level
3)
Disable standby-light:
1. Briefly press „Lock/Unlock": Programming mode
2. Briefly press „Time"
3. Briefly press „4"
4. Briefly press „On/Off": Standby-light is switched on or off respectively
5. Briefly press „Lock/Unlock": Operating mode
Standby-light level may be set from 0.1 to 51%:
1. Briefly press „Lock/Unlock": Programming mode
2. Press „Dim+" or „Dim-" respectively: level is set
3. Briefly press „Lock/Unlock": Operating mode
2.12 Setting of sensitivity (1)
The sensitivity of the detector can be set.
To do so, please proceed as follows:
1. Briefly press "Lock/Unlock" button: Programming mode
2. Briefly press "Sens" button and then "1" for maximum sensitivity,
"2" for high sensitivity, "3" for low sensitivity or "4" for minimum sensitivity.
3. Briefly press "Lock/Unlock" button: Operating mode
Example: The detector needs to work with maximum sensitivity. Press the "Lock/Unlock" button; the green LED
switches on. Then press "Sens" and "1". Finally, press "Lock/Unlock" again; the green LED switches off.
2.13 Reset to default settings
If the detector needs to be reset to its default settings, meaning into the "Out-of-the-box" setup mode, please
proceed as follows:
1. Press "Lock/Unlock" button: Programming mode
2. Press and hold "Fact. set" button for about 4 s until the green LED switches off briefly as a confirmation.
3. Press "Lock/Unlock" button: Operating mode
The detector was reset to its default settings and must be newly set up,
which means all DALI devices must be readdressed.
2.14 Burn-in activation (100 h)
During the start-up or prior to the replacement of fluorescent tubes, a burn-in of the tubes must be carried out to
optimise the operating life. During the burn-in process, the detector operates the lights with an output of 100%.
The daylight control is switched off as long as the burn-in function is active and activity is registered in the detection
area. After the completion of the burn-in process, the detector automatically switches back to daylight control.
As long as the burn-in function is active, the lighting can neither be dimmed via the buttons nor via the P-IR remote
controls. In case of a power supply disruption, the detector saves the lapsed time of the burn-in function and the
time measurement will be continued as soon as the power supply is restored. The active burn-in process is indicated
by a yellow LED, which blinks once per second when the detector is in operating mode.
Activation of the burn-function:
1. Press "Lock/Unlock" button: Programming mode
2. Press "Burn in" button to activate or deactivate the burn-in function.
a. Green LED flashes 1x
b. Green LED flashes 2x
3. Press "Lock/Unlock" button: Operating mode
In the operating mode, the red and green LED are switched on simultaneously when the burn-in function is active.
Status display
Press "Status" to read out the status of inidvidual parameters on the detector. Parameters are displayed in operating
mode by the flashing of the green LED. If the green LED does not light up, the device is not yet initialised. Await the
flashing signal before repressing any buttons.
2.15 Status – time (4)
To read the individual times, first press "Status" and then "Time".
Time 1 = delay, Time 4 = Standby-light.
Depending on which time needs to be applied, press "1" for Time 1 or "4" for Time 4.
The detector indicates the time respective number of blinking signals from the LED.
Time (min)
Number of flashing
light signals, green
Example 1: Reading of the delay time 1: Press the "Status" button, then "Time" and "1". The green LED flashes 3
times, which means that the delay time has been set to 15 min.
2.16 Status - Illumination level
To display the programmed illumination level, first press "Status" and then "Lux".
The detector indicates the illumination level values through a respective number of blinking signals from the LED.
Lux (lx)
Number of flashing
light signals, green
Example: Display of the required illumination level: Press "Status" button and then "Lux".
The green LED flashes 3 times, which means that the required illumination level has been set to 300 lx.
>1m
z
x
Time 1
3 s
ON
Time 4
Stand-by
OFF
t
Delay
Standby-light
Burn-in active
Burn-in inactive
5
10
15
30
45
1
2
3
4
100
200
300
400
600
1
2
3
4
5
6
DA
DA
N
5
7
2.17 Status – sensitivity
To display the programmed illumination level, first press "Status" and then "Sens.".
The detector indicates the sensitivity through a respective number of blinking signals from the LED.
Sensitivity
Number of flashing
light signals
Example 1: Press "Status" button and then "Sens.". The green LED flashes 2 times,
which means that a high sensitivity has been set.
2.18 Status – Burn-in
The status of the burn-in function is indicated by LED blinking signals on the detector. The number of blinking signals
of the green LED indicates the number of hours that the burn-in function remains active. However, if the red LED blinks
once, it means that the burn-in function is not active.
Press "Status" button and then "Burn in". The detector indicates the remaining time in 10 hours intervals.
If the red LED is illuminated, the Burn-in function is inactive.
Burn-in
Number of flashing
light signals, green
Example 1: Reading of the burn-in status. Press "Status" button and then "Burn in".
The green LED flashes twice, the remaining time of the burn-in function is 20 h.
2.19 Status - zones
Which device is allocated to which zone can be indicated by first pressing "Status" and then "1" for Zone 1, "2" for
Zone 2 or "3" for Zone 3. All devices of the selected zone switch on for 5 seconds while all others will be switched off.
After the expiration of the 5 s, all devices in all zones switch back to their original status.
Example: It needs to be determined which devices are allocated to Zone 2. Press the "Status" button and then "2" for
Zone 2. All lights allocated to Zone 2 will be switched on for 5 s with 100% output and all potential relays will also be
activated for 5 s. All other units will be switched off.
2.20 Status - minimum lighting or switch off
To determine whether the lighting switches off or switches to minimum output in the daylight zones during illumina-
tion, press the "Status" and the "Min/Off" button. The red LED on the detector blinks when the device is switched to
minimum output or the green LED flashes when the lighting is switched off.
Example: Display of the setting of the lighting in the daylight zones during illumination. Press "Status" button and
then "Min/Off". A red LED blinks on the detector which means that the lighting in the daylight zone remains switched
on during the illumination at minimum output.
2.21 Status - AUTO or SEMI-AUTO functions with automatic switch off
To display the setting, press the "Status" button and then "On/Off". If the red LED blinks on the detector,
the AUTO function is active via the detector. The green LED flashes, the SEMI-AUTO function is active with
automatic switch off via the detector.
Example 1: Press "Status" button and then "On/Off". The red LED on the detector blinks once, which means that
Zone 1 has been programmed for AUTO.
2.22 Switch all zones on and off
With the "On/Off" button, all zones can be switched on and off.
2.23. Dim all zones
With the "Dim +" of "Dim -" buttons, the lighting in those zones can be amplified or reduced.
"Dim +" or "Dim -" must be pressed until the desired lighting level has been reached. Then release the button.
As long as one of the buttons is pressed, the green LED flashes.
2.24 Switching on/off and dimming certain zones
Instead of maintaining control of all zones, they can also be individually selected and individually controlled.
To do so, first select the desired zone: Press "1" for Zone 1, "2" for Zone 2 or "3" for Zone 3, then the function
buttons "On/Off" or "Dim +" or. "Dim -". After selecting the zone, e.g. button "1", the function button must be pressed
within 4 s.
Example 1: Switching Zone 1 on and off. Press button "1" and then "On/Off".
The detector activates the daylight control and switches all devices in Zone 1 either on or off.
To reactivate the automatic daylight control, press "Auto".
Example 2: The lights in Zone 2 need to be dimmed. Press button "2" and then "Dim -".
The daylight control is deactivated and the lights in Zone 2 are dimmed as long as the "Dim -" button is kept pressed
and the green LED flashes. Release the button when the desired illumination level has been reached, the green LED
does not blink any more.
To reactivate the automatic daylight control, press "Auto".
Note: When you have selected a zone, e.g. "1" for Zone 1, and a function, e.g. "On/Off", but you want to activate a
different function, please wait 4 s and then select a different function. During this time Zone 1 remains activated.

3. LED status display

Status
"Out-of-the-box"
Unlock
Lock
60
Off (only Time 4)
5
6
7
8
Zone allocation
Test mode
P-IR remote control
(accessories)
Dim +
Dim -
Illumination level
800
1000
set manually
Burn-in
6
7
8
The crossed-out wheeled dust bin symbol indicates that products must be
collected and disposed of separately from household waste. Use an official
collecting point or contact your retailer where the product was purchased.
L
L
N
Zone 1–3 DA
+
DA
-
DA DA
Master
Slave
5 mm
90 mm
Maximum
High
Low
1
2
3
≤ 10 h
≤ 20 h
≤ 30 h
≤ 40 h
≤ 50 h
≤ 60 h
≤ 70 h
1
2
3
4
5
6
7
Display
The detector is connected but not yet initialised.
The green LED lights up while the detector is programmed and
ready for setup via the P-IR remote control.
The green LED switches off. The programming mode of the detector is completed and all
executed changes are saved.
The green LED briefly switches off when a correct selection has been made.
When the green LED switches off for 1 s and the red LED switches on for 1 s,
the allocation of the device to a zone was unsuccessful.
The green and red LED flash in sequence.
Each time when the detector receives a signal confirmed via the P-IR remote control,
it is confirmed by a brief switch off of the green LED when it is in programming mode.
If it is in operating mode, the green LED flashes briefly.
The green LED blinks as long as the button is pressed.
The green LED blinks as long as the button is pressed.
the red and the green LED are switched on continuously
When the function is active,
Minimum
4
≤ 80 h
≤ 90 h
≤ 100 h
8
9
10
.