  • Page 1 Swiss Garde 360 Presence Dimm / Slave Operating instructions...
  • Page 2 Swiss Garde 360° dimmer motion detector for flush ceiling installations; includes continuous light controller Characteristics: • The SG360P dimmer includes a continuous light controller! • 1–10 V interface for 50 dimmable electronic ballasts • Relay output including switched L’ phase •...
  • Page 3 Please note • Any work on the mains power supply must only be completed by trained specialists. • The installation must be completed in accordance with country-specific guidelines/ standards. • Disconnect the 230 V power supply before starting the installation! •...
  • Page 4 Connection diagram for a standard installation electronic ballast 1–10VDC 1–10 VDC SG 360 Dimm push SG 360 Dimm push button button (option) (option) L’ L N N L’ L 1–10VDC push SG 360 Dimm button (option) L’ L N N Installation version 1: Installation version 2: The electronic ballast receives a...
  • Page 5 Master device: rear view Slave device: rear view – 5 –...
  • Page 6 SG360P dimmer master controller STBY% TIME SENS SG360P dimmer slave SENS – 6 –...
  • Page 7: Controller Settings

    Controller settings LUX (twilight sensor) The lux controller can be adjusted from approx. 10 lx ( Test to 2000 lx ( Test 20 m 10 s 10 m TIME Test The timer can be used to determine how long the light will remain 20 m 10 s TIME...
  • Page 8 The following values apply to the diameter of the coverage area: Ø 8.5 m Ø 10 m Ø 12 m Ø 14 m Ø 16 m Installation height [m] Coverage area Ø [m] – 8 –...
  • Page 9: Initial Operation

    Initial operation • After being switched on, the initialisation process of approx. 30 s is started. • During the initialisation phase, the red LED is lit up and the connected light is switched on. The light and the LED are then switched off again. Depending on the program selected by the IR dimming remote control or the settings on the controllers, the detector now selects auto/test or short pulse mode.
  • Page 10 Dimming function Automatic dimming function (continuous light controller). The brightness value is automatically maintained at the preset lux value. Manual dimming function The intensity of the light can be adjusted manually using an external button, which must be pressed and held for more than two seconds. Dimming can be set to: 10% > 50% > 100% >...
  • Page 11 Operating modes: automatic/semi-automatic The button can be used to set the automatic or semi-automatic operating mode. To be able to do this, the detector must be in programming mode (unlocked). When the button is pressed, a beep sounds from the buzzer and the LED flashes once.
  • Page 12 Please note: When the, button is pressed the detector takes on the lux values set on the controller and the remote control takes on the initial values. Semi-automatic mode In semi-automatic mode, the light must always be switched on using the button on the remote control or via an external switch.
  • Page 13 Manual activation Automatic dimming and deactivation If the ambient lighting falls below the preset lux value, the light can be switched on by briefly pressing the external switch. The light is then automatically adjusted to the preset lux value. This will remain the same as long as there are people moving in the coverage area of the detector.
  • Page 14 IR dimming remote control General information: Hold the remote control towards the detector. The LEDs on the detector light up twice as confirmation. – 14 –...
  • Page 15 Button Function button Lock button – Activates/opens programming mode The detector can be programmed using the IR remote control. To do so, the programming mode must first be activated/opened: When the button is pressed, a beep sounds from the buzzer and the LED flashes briefly (0.2 s).
  • Page 16 Button Function button Cursor key and button to set Settings (lux value) = 100 lx Use the cursor to select the required set value in the = 300 lx lux category and press the button to submit to the detector. = 500 lx = 800 lx Settings...
  • Page 17 Button Function button Test mode is activated by pressing the button (remote control when in programming mode). The light is switched on for three seconds and then remains switched off for 6 s. By pressing the button again, it switches back to automatic opera- tion.
  • Page 18 Button Function button This button is used to manually switch the light on and off. This button is used to automatically or semi-automatically set the operat- ing mode. (Remote control when in programming mode). When the button is pressed, a beep sounds from the buzzer and the LED flashes once.
  • Page 19: Troubleshooting

    Troubleshooting Fault Cause/repair Electric load does not switch: • Twilight value is set too high • Check the light’s lamp • Check mains power supply/fuse Switches on and off: • Check coverage area for something causing the fault: drafts, animals, heating etc. can all cause an error to occur! •...
  • Page 20: Technical Specifications

    Swiss Garde 360 Presence Dimm Range Ø 16 m Model Description Art.-No SG360P Dimm Motion detector 360° Dimm Master 25160 SG360P Dimm Slave Motion detector 360° Dimm Slave 25360 Handheld IR Handheld PIR dimming 25350 – 20 –...