GE AF-600 FP Operating Instructions Manual page 159

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Mains Supply 3 x 525- 600 VAC
Typical Shaft output at 550 V [kW]
Typical Shaft output at 575 V [HP]
Unit Size IP21
Unit Size IP54
Unit Size IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec overload)
(at 550 V) [A]
Continuous
(at 575 V) [A]
Intermittent (60 sec overload)
(at 575 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Max. input current
Continuous
(at 550 V ) [A]
Continuous
(at 575 V) [A]
Max. cable size, mains, motor and
load share [mm
Max. cable size, brake [mm
(AWG)]
Max. external pre-fuses [A]
Estimated power loss
at rated max. load [W]
Weight,
Unit Size IP21, IP 54 [kg]
Weight,
Unit Size IP00 [kg]
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
P250
250
350
42
42
44
360
396
344
378
343
343
355
339
2 x 185
2
(2 x 350 mcm)
(AWG)]
2
2 x 185
(2 x 350 mcm)
1
500
5821
4)
151
138
4)
0 - 600 Hz
110 °C
60 °C
AF-600 FP High Power Operating Instructions
P315
315
400
42
42
44
418
460
400
440
398
398
408
390
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
550
6149
165
151
0.98
0 - 500 Hz
110 °C
60 °C
P355
355
450
51
51
52
470
517
450
495
448
448
453
434
8
4 x 240
(4 x 500 mcm)
2 x 185
(2 x 350 mcm)
700
6449
263
221
0 - 500 Hz
85 °C
68 °C
157