Table 3.7: Unit Size 41, 42, 43, and 44, 525-600 V
AF-600 FP
Bussmann PN*
450 HP
170M4017
500 HP
170M4017
600 HP
170M6013
650 HP
170M6013
Table 3.8: Unit Sizes 51 and 52, 525-600 V
AF-600 FP
Bussmann PN*
750 HP
170M7081
950 HP
170M7081
1050 HP
170M7081
1150 HP
170M7081
1350 HP
170M7082
Table 3.9: Unit Sizes 61, 62, 63, and 64, 525-600 V
AF-600 FP
Bussmann PN*
750 HP
950 HP
1050 HP
1150 HP
1350 HP
Table 3.10: Unit Sizes 61, 62, 63, and 64, 525-600 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use.
3.1.14 Motor Insulation
For motor cable lengths ≤ the maximum cable length listed in the General Specifications tables the following motor insulation ratings are recommended because
the peak voltage can be up to twice the DC link voltage, 2.8 times the mains voltage, due to transmission line effects in the motor cable. If a motor has lower
insulation rating it recommended to use a du/dt or sine wave filter.