3.4
POSITIONING THE HEATING
CONTROL UNIT
Special attention must be paid to local standards and regulations
regarding heating control units, especially the minimum distances
that must be observed.
Installation must be comply with the requirements contained in the
most recent standards and legislation regarding heating control units,
heating system installation and hot water production, ventilation, flues
suitable for condensation boiler combustion product exhaust, and any
other applicable regulation.
A > 400 mm
B > 400 mm
C = 100 mm
D = 500 mm
Observe the minimum clearance distances required to
perform normal maintenance and cleaning operations.
Instructions for the installer
The boiler can be placed on a flat platform that is sufficiently sturdy
in size, in plan, no smaller than the boiler measurements and with a
minimum height of at least 100 mm so that the trap for condensate
drainage can be installed. Alternatively, a trap can be built from this
platform, next to the boiler, at a depth of 100 mm so that the trap can
be placed in it (Parag. 3.16).
When installation is complete the boiler should be perfectly horizontal
and firmly stable (to reduce vibrations and noise).
A
C
17
B
D
Sifone
Trap