Bcm. Prameters - Immergas ARES 440 TEC ERP Instructions And Warnings

Modular condensing boiler
Hide thumbs Also See for ARES 440 TEC ERP:
Table of Contents

Advertisement

Inspections and maintenance
4.4
BCM. PARAMETERS
BCM parameters - ARES TEC 440 - 550 - 660 - 770 - 900
Code
Symb.
803
Srv
Services Enabled
483
rP
Gen: Temp. Max Differential
34
HY
Burner Hysteresis
31
HL
CH#1: Minimum Setpoint
39
HH
CH#1: Maximum Setpoint
799
AC
Input 0/10V
376
DI1
Programmable Input #1
322
Po
Pump Post-circulation
341
PL
Pump Minimum Control
313
Pr
Pump Maximum Control
792
CHP
CH: Max Modulation
611
POT
Gen: Err. Max. Parallel
612
POL
Gen: Mod. Max. Parallel
650
dL
DHW: Minimum Setpoint
385
dH
DHW: Maximum Setpoint
360
dt
Storage tank adjustment
656
drT
DHW: Temp. Request Differential
657
drH
DHW: Request Temp. Hysteresis
310
DpT
DHW Pump: Postcirc.
660
dbT
DHW: Temp. Boiler Maximum
48
ChSet
CH#1: Setpoint
64
ChPO1
CH#1: Parallel Supply
346
FL
Minimum Modulation
600
mB
Burners: Min. Inserted
616
BSt
Gen: Insertion Time
613
BRt
Gen: Removal Time
336
HS
Temperature Gradient
353
HP
CH PID: Proportional
354
HI
CH PID: Integrative
478
Hd
CH PID: Derivative
816
MI
ModBus Address
817
MT
Timeout Modbus
896
TU
°Fahrenheit
309
St
Application Code
368
VA1
Programmable Relay #1
369
VA2
Programmable Relay #2
771
PS
Water Pressure Sensor
768
LG
Min. Gas Pressure Sens.
793
COC
Chimney Obstruction Sens.
622
FS
Minimum Flow Sensor
Description
48
Unit
Min
Max
16
27
°K
0,0
50,0
°K
5,0
20,0
°C
20,0
40,0
°C
45,0
85,0
0
3
0
2
min.
1
10
V
0
10
V
0
10
%
0
100
°K
0
30
%
0
100
°C
25,0
45,0
50,0
65,0
0
15
°K
-20
20
°K
1
20
sec.
5
600
°C
50,0
85,0
°C
20,0
85,0
0
1
%
0
100,0
1
8
sec.
30
900
sec.
30
900
°C/min
1
30
°K
0
50
°K
0
50
°K
0
50
1
127
sec.
0
240
0
1
0
1
0
1
0
1
0
1
0
1
0
2
0
1
Factory settings
19
25
5,0
35,0
85,0
1
3
5
3
10
100
5
0
35,0
65,0
0
4
8
60
75,0
85,0
0
25,0
1
120
120
5
25
12
0
1
30
0
0
0
1
0
0
0
0

Advertisement

Table of Contents
loading

Table of Contents