Inspections And Maintenance; Instructions For Inspection And Maintenance - Immergas ARES 440 TEC ERP Instructions And Warnings

Modular condensing boiler
Hide thumbs Also See for ARES 440 TEC ERP:
Table of Contents

Advertisement

4
INSPECTIONS AND
MAINTENANCE
4.1
INSTRUCTIONS FOR INSPECTION
AND MAINTENANCE
Inspections and maintenance carried out to state
of the art and at regular intervals, as well as the
exclusive use of original spare parts, are of primary
importance for smooth operation and to guarantee
long boiler life.
Annual maintenance of the appliance is compulsory,
in accordance with Legislation in force.
Failure to carry out Inspections and Maintenance can
cause material and personal damage.
For this reason we recommend stipulating an inspection or maintenance
contract.
Inspection is required to determine the effective state of an appliance
and compare it with the optimal state. This is carried out through
measuring, checking, observing.
Maintenance is required to eliminate any deviation of the effective state
from the optimal state. This is usually carried out through cleaning,
setting and possibly replacing single parts that are subject to wear.
These maintenance intervals
are set forth by a specialist based on the
certified state of the appliance at the time of inspection.
Table of resistance values based on the heating probe (SR) and the
heating return probe (SRR) temperature.
T°C
0
0
32755
31137
10
20003
19072
20
12571
12019
30
8112
7775
40
5363
5152
50
3627
3491
60
2504
2415
70
1762
1703
80
1263
1222
90
920
892
Relation between the temperature (°C) and nom. resistance (Ohm) of
the heating probe SR and the heating return probe SRR.
Example: At 25°C, the nominal resistance is 10067 Ohm
At 90°C, the nominal resistance is 920 Ohm
1
2
3
29607
28161
18189
17351
11493
10994
7454
7147
4951
4758
3362
3238
2330
2249
1646
1592
1183
1146
865
839

Inspections and maintenance

Instructions for inspection and maintenance.

Only original spare parts must be used to ensure a
long life for all of the functions of your appliance,
and to avoid changing the conditions of the approved
standard product.
Before proceeding with maintenance operations, always carry out the
procedures described below:
- Turn off the mains switch.
- Separate the appliance from the electrical network using a separation
device, with a contact opening of at least 3 mm (for ex. safety devices
or power switches), and make sure it cannot be accidentally re-
connected.
- Shut the gas cut-off valve upstream of the boiler.
- If necessary, and based on the work that needs to be carried out, close
any cut-off valves on the heating flow and return.
Once the maintenance work has been finished, always carry out the
operations listed below:
- If necessary, open the heating flow and return
- Relieve and, if necessary, restore the pressure in the heating system.
- Open the gas cut-off valve.
- Re-connect the appliance to the electrical network and engage the
mains switch.
- Make sure the appliance is water-tight, on the gas side and the water
side.
OBLIGATION!
Wear protective gloves.
Scalding hazard!
Be careful during the maintenance operations.
4
5
6
26795
25502
24278
16557
15803
15088
10519
10067
9636
6855
6577
6311
4574
4398
4230
3119
3006
2897
2171
2096
2023
1539
1488
1440
1110
1075
1042
814
790
766
41
7
8
9
23121
22025
20987
14410
13765
13153
9227
8837
8466
6057
5815
5584
4069
3915
3768
2792
2692
2596
1954
1888
1824
1393
1348
1304
1010
979
949
744
722
701

Advertisement

Table of Contents
loading

Table of Contents