Burst Mode

This device does not support Burst-Mode.
4.4.1

Catch Device Variable

This device does not support Catch Device Variable.
4.5

Device-specific commands

4.5.1

Command #130: Read. User Login

Operation: READ
The access level of the HART fieldbus interface can be changed with this command.
By writing a wrong PIN or by timeout the HART-Access-Level falls back to the default access
level.
The HART Access-Level is falling back to RUP after 10 minutes. Timeout is restarted with
every Write-Access over HART.
Byte
None
FCT030 HART (From firmware 4.0)
Function Manual, 06/2018, A5E39931617-AB
Function
Trim Loop Current Zero
Trim Loop Current Gain
Read Dynamic Variable Assignments
Write Dynamic Variable Assignments
Write Device Variables Units
Read Device Variables Information
Write Number Of Response Preambles
Read Analog Channel And Percent Of Range
Read Analog Channel Information
Read Analog Channel Endpoint Values
Read Device Communications Statistics
Format
4.5 Device-specific commands
Description
HART commands