Commissioning
3.6 Adding device to communication network
1. Add the device to SIMATIC HART network:
– Select File → New. Type in a project name, for example FC430 commissioning.
– Go to View and select Process Device Network view.
– Right-click on the typed in Project name and select Insert New Object → Networks.
– Right-click on Networks and Insert New Object → Communication Network.
– Click on Assign Device Type and select HART Modem Network. Click OK two times. Your
PC is now added to the HART Modem Network.
– Right-click on HART Modem Network and select Insert New Object → Object.
– Click on Assign Device Type, and select Devices → HART → Sensors → Flow → Coriolis →
SIEMENS AG → SITRANS FC430 Click OK two times.
Figure 3-2
2. Set up the communication parameters for SIMATIC HART modem network:
– Select Networks → My computer, right-click on COM Port Interface and select Object
Properties.
– Select the Communication tab and configure the communication parameters.
16
Assigning a HART modem network
FCT030 HART (From firmware 4.0)
Function Manual, 06/2018, A5E39931617-AB