HART commands
4.7 HART specific information table
Modbus
Register
2442
2444
Table 4-28
Modbus
Register
8303
8403
8503
Note
After the command Reset or Preset has been send to the device, the command Totalize must
be send, to continue totalizing
52
Data type
Parameter
Size [bytes]
Float / 4
Density
Correction
Factor
Float / 4
Density
Correction
Offset
Totalizers
Data type
Parameter
Size [bytes]
Unsigned /
TOT1_SET Control totalizer 1
1
Unsigned /
TOT2_SET Control totalizer 2
1
Unsigned /
TOT3_SET Control totalizer 3
1
Description
Set density compensation
value (gain) in order to make
a density correction (scale
factor).
To increase the displayed
density value with +0.5 %,
set the density factor to 1.005.
The displayed density value
will now be 0.5 % higher than
before
Set density compensation
value (offset) in order to
make an offset on the meas‐
ured density.
Description
Function Manual, 06/2018, A5E39931617-AB
Default
Value
Access
value
range
level
1
-1.999 to
Read /
+1.999
Write
0
-1 400 to
Read /
[kg/m3]
+1 400
Write
Default
Value
Access
value
range
level
0
0: TOTALIZE
Read /
1: RESET
Write
2: PRESET
3: HOLD
0
0: TOTALIZE
Read /
1: RESET
Write
2: PRESET
3: HOLD
0
0: TOTALIZE
Read /
1: RESET
Write
2: PRESET
3: HOLD
FCT030 HART (From firmware 4.0)