Safety Diagnostics In The Input Data Image (Idi); Safety Diagnostics Of Safe As-I Inputs - Pepperl+Fuchs CC-LINK Series Compact Manual

Table of Contents

Advertisement

CC-Link Gateways
Diagnostics
Paragraph A:

Safety diagnostics of safe AS-i inputs

Diagnostics in the IDI is a way of sending the key diagnostics functions to the
controller without a command interface (Mailbox) or any additional effort. The dia-
gnostics information is sent in the input data image, coded for the input bits of the
address of the safety input slave.
The switching state of Channels 1 and 2 of the safety input is shown with negli-
gible time lag in bits 0 and 1 and can be directly read:
Bit3
Bit2
X
X
X
X
X
X
X
X
Bits 2 and 3 are used to send the status of the safety input (the device color of the
ASIMON):
Bit3
Bit2
0
0
0
1
1
0
1
1
38

Safety diagnostics in the Input Data Image (IDI)

Bit1
Bit0
Description
0
0
Both channels open
0
1
nd
2
channel open, 1
1
0
nd
2
channel closed, 1
1
1
Both channel closed
Bit1
Bit0
Description
X
X
Device color: red, green or gray
X
X
Device color: yellow ("waiting")
X
X
Device color: yellow flashing ("testing")
X
X
Device color: red flashing ("Error")
st
channel closed
st
channel open
Tab. 8-43. Stae of safety input