Temperature And Resistance Relationship Tables (For Sensors) - Bosch BOVA Series Installation Instructions Manual

2.0 split system heat pump, condensing units up to 20.5 seer, 2-3-4-5 ton capacity, r410a
Hide thumbs Also See for BOVA Series:
Table of Contents

Advertisement

3 6 | Bosch IDS 2.0 BOVA

15.12 Temperature and Resistance Relationship Tables (for Sensors)

TEMP F
TEMP C
-5
-20.6
0
-17.8
5
-15.0
10
-12.2
15
-9.4
20
-6.7
25
-3.9
30
-1.1
40
4.4
45
7.2
50
10.0
55
12.8
60
15.6
65
18.3
70
21.1
75
23.9
80
26.7
85
29.4
Table 24
for T3, T4, Th, T3L
Data subject to change
RESISTANCE kΩ
VOLTS DC
107.732
4.65
93.535
4.60
79.521
4.54
67.795
4.47
57.948
4.39
49.652
4.30
42.645
4.21
36.710
4.10
27.386
3.86
23.732
3.73
20.610
3.59
17.939
3.45
15.648
3.30
13.681
3.15
11.987
2.99
10.527
2.83
9.265
2.67
8.172
2.52
TEMP F
TEMP C
RESISTANCE kΩ
90
32.2
95
35.0
100
37.8
105
40.6
110
43.3
115
46.1
120
48.9
125
51.7
130
54.4
135
57.2
140
60.0
145
62.8
150
65.6
155
68.3
160
71.1
165
73.9
170
76.7
Installation Instructions
VOLTS DC
7.225
2.36
6.401
2.21
5.683
2.07
5.057
1.93
4.509
1.79
4.028
1.67
3.606
1.55
3.233
1.43
2.902
1.32
2.610
1.22
2.350
1.13
2.119
1.04
1.914
0.96
1.731
0.88
1.574
0.82
1.416
0.75
1.276
0.68
02.2019 | Bosch Thermotechnology Corp.