15.9 Parameter Point Check Table

To display system parameters, press the "Check" button to index through
the series of parameters available. The first time you press the "Check"
button, it will display the sequence, and after 1 second it will display the
value of the parameter. If you press the "Check" button again, it will display
the next sequence. Refer to Figure 44 and 45 for check button location on
the control board.
Normal Status, last two digits will display under the following conditions
i.
Unit not operating (Standby Mode); "outdoor ambient temperature".
ii.
Unit operating; displays "compressor operating frequency".
After 20 seconds on same parameter, the display will revert back to normal
status.
If a system protection is active, first digit will display "status code".
No.
Point check content
0
Outdoor unit capacity
1
Outdoor unit mode
2
Outdoor unit set compressor speed (Hz)
3
T3 (outdoor coil temp.) (°F)
4
T4 (outdoor ambient temp.) (°F)
5
T5 (compressor discharge temp.) (°F)
6
Th (compressor suction temp.) (°F)
7
T3L (liquid line temp.) (°F)
8
Tf (module temp.) (°F)
9
Pe (evaporating pressure) (PSI)
10
Pc (condensing pressure) (PSI)
Tes target of the evaporating temp. (only use for cooling
11
mode) (°F)
12
Te (evaporating temp.) (°F)
Tcs target of the condensing temp. (only use for heatling
13
mode) (°F)
14
Tc (condensing temp.) (°F)
Target of the compressor discharge superheat (only use for
15
heating mode) (°F)
16
Compressor discharge superheat (°F)
17
Openings of EEV
18
Fan speed
19
Compressor current (A)
20
Power AC voltage Input (V)
21
Compressor input dc voltage (V)
22
Continuous running time of the compressor (min)
23
Last fault code
24
Software version
25
Remark"--"
Table 14
Bosch Thermotechnology Corp. | 02.2019
Example
Remark
H3
H3=Heat Pump 3 ton
0 standby,
2
2 cooling,
3 heating
66
Low Suction Pressure
High Head Pressure
00
see Table 9-4
01
--
--
Bosch IDS BOVA | 27
Data subject to change