Bosch BOVA Series Installation Instructions Manual page 32

2.0 split system heat pump, condensing units up to 20.5 seer, 2-3-4-5 ton capacity, r410a
Hide thumbs Also See for BOVA Series:
Table of Contents

Advertisement

3 2 | Bosch IDS 2.0 BOVA
P4 (High compressor discharge temperature (T5) protection)
Diagnosis
Check whether the service
valves are open
Yes
Check whether the T5 is normal
according to Table 25 (between
temperature and resistance)
Yes
Check whether outdoor and
indoor unit motor is abnormal
or whether coils(outdoor and
indoor) are blocked
No
Check whether the charge is
correct by subcooling
according to installation guide
in charge mode when cooling
Yes
Check whether the EEV/TXV is
normal for throttle
(wire seated .coil)
Yes
Check whether the compres-
sor is normal (abnormal noise,
abnormal vibration)
Yes
Figure 51
Data subject to change
Handling
No
Open the service valve
No
Replace the T5 sensor
Yes
Replace the fan or
remove all the barriers
No
Adjust the charge
Re-power and check
No
again,if the same, replace
the EEV/TXV.
No
Replace the compressor
Error Code
Description
E4
Temperature sensor fault (T3, T4, T5,Th, T3L, TF)
H8
Pressure transducer (PT) fault
F1
High pressure switch (HPS) fault
Table 18
E4 (Temperature sensor fault (T3, T4, T5, Th, T3L, TF)
Diagnosis
Check whether sensor
T3/T4/T5/Th/T3L/TF are
seated and normal
(T4 for Heat Pump only)
Yes
Unplug the sensor, check
whether the resistance of
T3/T4/Th/T3L is in the range
of Table 24
Yes
Unplug the sensor, Check
whether the resistance of T5/Tf
is in the range of Table 25
Yes
Check whether the display the
shows the same error code
when re-powered on
Yes
Figure 52
H8 (Pressure transducer (PT) fault)
Diagnosis
Check whether pressure
transducer(PT) wiring are
seated and normal
Yes
Is the pressure transducer
working properly? Compare
the data between pressure
measurement and No 9
(cooling) or No 10 (heating)
check point value (by pressing
check button)
Yes
Check whether there is the
same fault
Yes
Figure 53
Installation Instructions
Handling
No
Reseat the sensor
according to wiring diagram
No
Replace the fault T3/T4
Th/T3L sensor
No
Replace the fault T5/Tf sensor
No
Keep running
Handling
No
Wire according to the
diagram correctly
No
Replace the pressure
transducer
No
Keep running
02.2019 | Bosch Thermotechnology Corp.