Bosch BOVA Series Installation Instructions Manual page 22

2.0 split system heat pump, condensing units up to 20.5 seer, 2-3-4-5 ton capacity, r410a
Hide thumbs Also See for BOVA Series:
Table of Contents

Advertisement

2 2 | Bosch IDS 2.0 BOVA
3.
Stabilize the system.
After starting the system in cooling mode, short press "FORCE" button,
and " " symbol should appear. System may take 10 minutes to ramp up.
Operate the system for a minimum of twenty (20) minutes.
After a twenty (20) minute stabilization period operating at 100%
capacity (i.e. once the compressor reaches the frequency shown in Table
6), maintain continuous operation while adjusting refrigerant charge.
After adjusting, operate system for a minimum of fi ve (5) minutes for
system to stabilize, otherwise repeat step 3.
Compressor Frequency in Force Mode in Cooling
ODU Capacity
2TON
Frequency (HZ)
48
Table 6
20 MIN.
Figure 39
4.
Calculate superheat value (According to Table 7)
Measured Suction Line Temp = ________ºF
Measured Suction Line Pressure = _______ PSIG
Calculate superheat value = ________ºF
  C heck the superheat and select correct subcooling according to
superheat, refer to Table 9. It is recommended to keep the superheat at
10-18°F if a third party indoor unit is used.
5.
Calculate subcooling value (According to Table 8)
Measured Liquid Line Temp. = ________ºF
Measured Liquid Line Pressure = _______ PSIG
Calculate subcooling value = ________ºF
Figure 40
Data subject to change
3TON
4TON
5TON
72
54
62
Insulation
If calculated subcooling value is lower than the design subcooling value
(Table 9), please add refrigerant. Repeat steps 3 through 5.
If the superheat is out of range, refer to Troubleshooting section of this
IOM.
Suction
Temp
6
8
10
12
(°F)
40
105
101
97
93
42
109
105
101
97
44
114
109
105
101
46
118
114
109
105
48
123
118
114
109
50
128
123
118
114
52
133
128
123
118
54
138
133
128
123
56
143
138
133
128
58
148
143
138
133
60
153
148
143
138
62
159
153
148
143
64
164
159
153
148
66
170
164
159
153
68
176
170
164
159
70
182
176
170
164
72
188
182
176
170
Table 7 R-410A Refrigerant chart - Final Superheat
Liquid
Temp
6
7
8
(°F)
Liquid Gauge Pressure (PSI)
55
173
176
179
60
188
191
195
65
204
208
211
70
221
225
229
75
239
243
247
80
259
262
266
85
279
283
287
90
300
304
309
95
322
327
331
100
346
351
355
105
370
376
381
110
397
402
407
115
424
430
435
120
453
459
465
125
483
489
469
Table 8
R-410A Refrigerant chart - Final Subcooling
Design Subcooling
Model
24K/36K
48K
60K
Table 9
Installation Instructions
Final Superheat (°F)
14
16
18
20
Suction Gauge Pressure (PSI)
89
86
82
78
93
89
86
82
97
93
89
86
101
97
93
89
105
101
97
93
109
105
101
97
114
109
105
101
118
114
109
105
123
118
114
109
128
123
118
114
133
128
123
118
138
133
128
123
143
138
133
128
148
143
138
133
153
148
143
138
159
153
148
143
164
159
153
148
Final Subcooling (°F)
9
10
11
12
182
185
188
191
198
201
204
208
215
218
221
225
232
236
239
243
251
255
259
262
270
275
279
283
291
295
300
304
313
318
322
327
336
341
346
351
360
365
370
376
386
391
397
402
413
418
424
430
441
447
453
459
471
477
483
489
502
508
515
521
Subcooling/℉
Superheat/℉
10±2
10―18
8±2
7―10
8±2
9―18
6±2
7―9
8±2
8―18
6±2
6―8
02.2019 | Bosch Thermotechnology Corp.
22
75
78
82
86
89
93
97
101
105
109
114
118
123
128
133
138
143
13
195
211
229
247
266
287
309
331
355
381
407
435
465
496
528