2 Unit Location Considerations

2.1 Unit Dimensions

Unit Dimensions
Models
BOVA-36
BOVA-60
Table 1
The unit's weight values are on the carton box.
When mounting the outdoor unit on a roof, be sure the roof will support the unit's
weight. Properly selected isolation is recommended to prevent sound or vibration
transmission to the building structure.
L
L
Figure 1

2.2 Refrigerant Piping Limits

Liquid
Suction
System
Line
Line
Capacity
25
Model
Inch O.D.
3/4 Std.
25
2 Ton
3/8 *
5/8 Opt.
25
3/4 Std.
25
3 Ton
3/8 *
5/8 Opt.
25
7/8 Std.
25
4 Ton
3/8 *
3/4 Opt.
25
7/8 Std.
25
3/4 Opt.
25
5 Ton
3/8 *
1 1/8 Opt.
25
Table 2
* Standard line size is recommended;
N/A: Application not recommended;
Refrigerant charge: refer to Sec. 14
Data subject to change
H x W x L (Inches)
24-15/16 x 29-1/8 x 29-1/8
33-3/16 x 29-1/8 x 29-1/8
W
W
H
H
Total Equivalent Length - Feet
50
75
100
125
Maximum Vertical Separation - Feet
50
45
40
30
50
45
40
30
50
50
50
35
50
50
50
35
50
50
40
30
50
50
40
30
50
50
40
30
50
50
40
30
40
N/A
N/A
N/A
Maximum line equivalent length = 150 feet.
Maximum vertical equivalent length = 50 feet.
Use only the line diameters indicated in Table 2.
If the suction linesets are greater than 50 feet, do not use a larger suction
line than recommended.
150
25
25
25
25
25
25
Figure 2
25
25
N/A
Installation Instructions
Standard Lineset
Lineset 150' Max
Line Length
50' Max
Line Lift
50' Max
Line Lift