2 0 | Bosch IDS 2.0 BOVA
13 Start Up
13.1 System Start Up
1.
Ensure Sections 7, 8, 9, 10, 11, and 12 have been completed.
2.
Set System Thermostat to OFF.
Figure 33
3.
Turn on disconnect to apply power to the indoor and outdoor units.
Figure 34
4.
Upon initial unit installation, wait one (1) hour before starting the unit if
compressor crankcase heater is used and the outdoor ambient temperature
is below 70 ºF.
60 MIN.
Figure 35
Data subject to change
ON
OFF
5.
Set system thermostat to ON.
Figure 36
Installation Instructions
02.2019 | Bosch Thermotechnology Corp.