Temperature And Resistance Relationship Tables (For Sensors) - Bosch BOVB 18 Series Installation Instructions Manual

Split system heat pump
Table of Contents

Advertisement

Installation Instructions

15.12 Temperature and Resistance Relationship Tables (for Sensors)

TEMP F
TEMP C
-5
-20.6
0
-17.8
5
-15.0
10
-12.2
15
-9.4
20
-6.7
25
-3.9
30
-1.1
40
4.4
45
7.2
50
10.0
55
12.8
60
15.6
65
18.3
70
21.1
75
23.9
80
26.7
85
29.4
Table 25
for T3, T4
Bosch Thermotechnology Corp. | 10.2020
RESISTANCE kΩ
VOLTS DC
107.732
4.65
93.535
4.60
79.521
4.54
67.795
4.47
57.948
4.39
49.652
4.30
42.645
4.21
36.710
4.10
27.386
3.86
23.732
3.73
20.610
3.59
17.939
3.45
15.648
3.30
13.681
3.15
11.987
2.99
10.527
2.83
9.265
2.67
8.172
2.52
TEMP F
TEMP C
RESISTANCE kΩ
90
32.2
95
35.0
100
37.8
105
40.6
110
43.3
115
46.1
120
48.9
125
51.7
130
54.4
135
57.2
140
60.0
145
62.8
150
65.6
155
68.3
160
71.1
165
73.9
170
76.7
Bosch IDS BOVB 18 | 37
VOLTS DC
7.225
2.36
6.401
2.21
5.683
2.07
5.057
1.93
4.509
1.79
4.028
1.67
3.606
1.55
3.233
1.43
2.902
1.32
2.610
1.22
2.350
1.13
2.119
1.04
1.914
0.96
1.731
0.88
1.574
0.82
1.416
0.75
1.276
0.68
Data subject to change